5.10
Refrigerant Charging
The refrigerant has been charged into the outdoor unit before shipped from the manufacturer, while
additional refrigerant still need be charged into the refrigerant pipe during the field installation.
5.10.1
Calculation of the Additional Refrigerant Charging
1)
Get the refrigerant charge of the outdoor unit from the nameplate.
Note:
The refrigerant charge of the outdoor unit does not include the charged additionally in the indoor unit,
DB module and the refrigerant pipe.
For the length of the connecting pipe is decided on the field, the amount of additional refrigerant shall
be decided depending on the dimension and the length of the liquid pipe used on the field.
Record the additional refrigerant charge for future maintenance.
It does not need to add refrigerant if the total length of liquid pipe is within 30m.
2)
Calculating the Mass of Additional Refrigerant
Additional Refrigerant Charge (kg) =
Σ
the Liquid Pipe Length of
Φ
6.35
×
0.022kg/m +
Σ
the Liquid Pipe
Length of
Φ
9.52
×
0.054kg/m
-
1.47(kg)
If the additional refrigerant charge is negative, it does not need to add the refrigerant.
3)
Example: MS-E56AIN
Serial No.
Model
Indoor unit 1
Cassette type MC-C12AI
Indoor unit 2
Duct type MC-D09AI
Indoor unit 3
Wall mounted type MS-H07AIZ
Indoor unit 4
Wall mounted type
MS-H09AIZ
Indoor unit 5
Duct type MC-D09AI
Indoor unit 6
Wall mounted type MS-H09AIZ
Serial No.
Diameter(mm)
Length(m)
L1
Φ
9.52 20
L2
Φ
9.52 10
L4
Φ
9.52 10
1A
Φ
6.35 5
1B
Φ
6.35 5
1C
Φ
6.35 5
2A
Φ
6.35 5
2B
Φ
6.35 5
2C
Φ
6.35 5
DB
DB
47
Summary of Contents for MS-E48AIN
Page 1: ...HIGH POWER MULTI SYSTEM SERVICE MANUAL EN MS E48AIN MS E56AIN Outdoor unit ...
Page 11: ...CONTROL 1 OPERATION FLOWCHART 6 ...
Page 13: ...1 2 Heating Operation 8 ...
Page 47: ... Outdoor unit higher than indoor unit DB DB DB DB 42 ...
Page 70: ...Malfunction display High Pressure Protection 2 1 65 ...
Page 87: ...PARTS GUIDE MS E48AIN MS E56AIN DB2 19SB DB3 19SB DB5 16AF HIGH POWER MULTI SYSTEM ...
Page 88: ...Exploded view of unitMS E48AIN ...
Page 91: ...Exploded view of unitMS E56AIN ...
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......