②
The bending diameter of the pipeline must be greater than 200mm. The connection pipe cannot often be
bent or straightened. Otherwise it will harden and crack.
③
If the thermal insulation of the refrigerant pipe is not removed, please do not bend the pipe. Otherwise, it
maybe leads the pipe to crack. It is better to make an incision with a knife in the thermal insulation and
removes it. After elbow operation is finished, recover the thermal insulation with binding band.
5.7.4 The process of install refrigerant pipes
①
Remove the screw caps from the pipes.
②
Align the flared end of copper tube with the center of pipe joint. Tighten the nuts by hands. (If the flared
end of copper tube and the center of pipe joint are not in coaxial, it is hard to tighten the nuts by hands,
please do not tighten it with spanners, because the screw thread may be broken by force).
③
Tighten the flaring nuts with torque wrench until you hear a “click”. (The spanner and torque wrench
should be perpendicular to the refrigerant pipeline).
④
The following table for the torque required to tighten the nuts.
Pipe diameter
Thickness of copper tube
Tightening torque
Φ
6.35 mm
≥
0.8 mm
15
~
30 N·m
Φ
9.52 mm
≥
0.8 mm
35
~
40 N·m
Φ
12.7 mm
≥
0.8 mm
45
~
50 N·m
Φ
15.9 mm
≥
1.0 mm
60
~
65 N·m
Φ
19.05 mm
≥
1.0 mm
70
~
75 N·m
Caution!
During the connection of the indoor unit and DB module to the refrigerant pipe, never pull any joints of the
indoor unit and the DB module by force; otherwise the capillary pipe or other pipe may crack, which then
would result in leakage.
The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of it.
For the Super Free Match system, each pipe should be labeled to tell which system it belongs to avoid
mistaken inaccurate piping.
45
Summary of Contents for MS-E48AIN
Page 1: ...HIGH POWER MULTI SYSTEM SERVICE MANUAL EN MS E48AIN MS E56AIN Outdoor unit ...
Page 11: ...CONTROL 1 OPERATION FLOWCHART 6 ...
Page 13: ...1 2 Heating Operation 8 ...
Page 47: ... Outdoor unit higher than indoor unit DB DB DB DB 42 ...
Page 70: ...Malfunction display High Pressure Protection 2 1 65 ...
Page 87: ...PARTS GUIDE MS E48AIN MS E56AIN DB2 19SB DB3 19SB DB5 16AF HIGH POWER MULTI SYSTEM ...
Page 88: ...Exploded view of unitMS E48AIN ...
Page 91: ...Exploded view of unitMS E56AIN ...
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......