The total length of the liquid pipes: 20+10+10+5+5+5+5+5+5=70(m).
Thus, the total length is over than 30m, so the air conditioner needs to add refrigerant.
Additional refrigerant charge
Σ
the Liquid Pipe Length of
Φ
6.35
×
0.022kg/m +
Σ
the Liquid Pipe Length of
Φ
9.52
×
0.054kg/m
-
1.47(kg)
=(5+5+5+5+5+5)(m)
×
0.022kg/m+(20+10+10)(m)
×
0.054kg/m
-
1.47(kg)
=1.35(kg)
4)
Additional refrigerant charge record
Diameter(mm)
Total length(m)
Additional refrigerant charge(kg)
Φ
6.35
Φ
9.52
Total
5.10.2
Procedures for adding refrigerant
NO.
1
2
3
4
5
Name
Outdoor unit
Service port
Liquid side stop valve
Gas side stop valve
Pressure-vacuum
gauge
NO.
6
7
8
9
Name Hi-knob Lo-knob
R410A
tank
Scale
1)
When the liquid and gas stop valves have not been opened, the system is under the vacuum:
①
Refer to the left of the figure; connect the R410A tank to the system.
②
Turn on the R410A tank and the Hi-knob; charge the R410A refrigerant into the system from the liquid
side stop valve. The Lo-knob should be closed completely.
③
Turn off the R410A tank and the Hi-knob immediately, when the adding refrigerant is enough.
④
Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and completely.
2)
If the pressure of the system is too high to charge refrigerant, you can do as follow.
①
Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and completely.
②
Turn on the power of the air conditioner, and set cooling mode, running more than 0.5h when outside
temperature is higher than 18
℃
DB.
a)
Refer to the left of the figure; connect the R410A tank to the system.
b)
Turn on the R410A tank and the Lo-knob, charge the R410A refrigerant into the system from the gas
side stop valve. The Hi-knob should be closed completely.
c)
Turn off the R410A tank and the Lo-knob immediately, when adding refrigerant is enough.
③
Turn on the power of the air conditioner, and set heating mode, running more than 0.5h when outside
temperature is lower than 18
℃
DB.
a)
Refer to the right of the figure, connect the R410A tank to the system.
b)
Turn on the R410A tank and the Hi-knob, charge the R410A refrigerant into the system from service
port. The Lo-knob should be closed completely.
48
Summary of Contents for MS-E48AIN
Page 1: ...HIGH POWER MULTI SYSTEM SERVICE MANUAL EN MS E48AIN MS E56AIN Outdoor unit ...
Page 11: ...CONTROL 1 OPERATION FLOWCHART 6 ...
Page 13: ...1 2 Heating Operation 8 ...
Page 47: ... Outdoor unit higher than indoor unit DB DB DB DB 42 ...
Page 70: ...Malfunction display High Pressure Protection 2 1 65 ...
Page 87: ...PARTS GUIDE MS E48AIN MS E56AIN DB2 19SB DB3 19SB DB5 16AF HIGH POWER MULTI SYSTEM ...
Page 88: ...Exploded view of unitMS E48AIN ...
Page 91: ...Exploded view of unitMS E56AIN ...
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......