9-8
Press the <
MORE INFO
> key to obtain the next display:
Device Address: 3-1
IDNet Device: M1-1
Press the <
NEXT>
key to obtain the next display:
1-Force on card LED Type: IDNet
IDNet CARD
Pressing key <
1
> will turn on the LED indicator on the IDNet Card in the FIP control rack and
pressing it again will turn the LED off. Press the <
NEXT>
key to move onto the next display.
1-Force on device LED Type: PHOTO
Variable Sensitivity PHOTO
Pressing the <1> key will turn on the LED indicator on the selected smoke detector and
pressing it again will turn it off. Press the <
NEXT>
key to move onto the next display.
Level 3 - Room 74
Smoke Detector ON-LINE
Press the <
NEXT>
key to move onto the next display to verify correct device type.
Level 3 - Room 74
Smoke Detector Correct Device
Press the <
NEXT>
key to display the current selected sensitivity.
Level 3 - Room 74
Present Sensitivity Selected - 3.7% Smoke
Note:
Sensitivity displayed is in % obscuration per foot.
%Obs/Ft %Obs/m
%Obs/Ft
%Obs/m
0.2% 0.6% 2.0% 6.5%
0.5% 1.6% 2.5% 8.2%
1.0% 3.3% 3.0% 9.8%
1.5% 5.0% 3.7% 12.1%
Table 9-1. Smoke Obscuration conversion chart.