5. Press the <1> key to enable/disable the Walk Test™ mode. The SYSTEM FAULT LED
illuminates, the tone-alert sounds, and the LCD displays the following message.
1 = ON>off 2 = no>LOG 3 = ?>ZONE 4 = NO<sig
WALK TEST GROUP 0
To enable multiple Walk Test™ groups, press the <NEXT> key to scroll to the next Walk
Test™ group. Then press the <1> key to enable that group. Continue scrolling, then press the
<1> key to select required Walk Test™ groups. Once all Walk Test™ groups are selected,
press the fault acknowledge key, then continue. When a Walk Test™ group with no
configured points is selected, the display shows the following message.
No walk test points configured for:
WALK TEST GROUP X
Note:
X equals 0 through 7.
When the Walk Test™ has been satisfactorily completed, exit from the Walk Test™ mode by
performing the following procedure.
1. Press the <MENU> key.
2. Press the <NEXT> key to select the Walk Test™ function.
3. Press the <ENTER> key.
4. Press the <1> key to turn off a Walk Test™ group. Press <NEXT>, then <1> to turn OFF
each enabled Walk Test™ group.
Note:
The system activates a one-minute timer when exiting from the Walk Test™ mode.
This timer ensures that monitor points have had ample time to clear (smoke) prior to
enabling the system. After the one-minute delay, the system Walk Test™ fault
automatically clears.
5. Press <MENU>. The Change Access Level menu is shown.
6. Press
<ENTER>.
7. Press <2> to log out.
8. If Access Level 4 was entered, a fault will continue to exist in the system. Access Level 4
is normally used by Simplex personnel and additional steps must be performed. Call
Simplex to restore the system.
9. Inform required personnel when system testing is completed.
Continued on next page
Walk Test™ PROCEDURES,
Continued
How to Enter Walk
Test Mode,
(
continued
)
How to Exit Walk
Test Mode