33
m
CAUTION
The total maximum length is obtained by adding the
length of the inlet and outlet pipes. The total load loss is
determined by the sum of the load losses of the single
accessories that make up the pipework. It should not
exceed 15 mmH
2
O. The total extension for each single
duct must not in any case exceed 25 m, even if the to-
tal load loss is less than the maximum which can be
applied.
NOTE:
for the boiler to operate correctly it is necessary that a
minimum distance of 0.50 m of the duct is respected with a 90°
inlet curve.
Example: calculation of the load loss of a
MURELLE.HT 25
boiler.
Accessories Ø
80 mm
Code
Quantity
Load loss (mm H
2
O)
Inlet
Outlet
Total
Extension W. 1000
mm (horizontal)
8077351
9
9 x 0,15
-
1,35
Extension W. 1000
mm (horizontal)
8077351
9
-
9 x 0,15
1,35
90° curve
8077450
2
2 x 0,20
-
0,40
90° curve
8077450
2
-
2 x 0,25
0,50
Wall terminal
8089501
1
0,10
-
0,10
Wall terminal
8089501
1
-
0,25
0,25
TOTAL
3.95
Installation is permitted as the total load losses (3,95 mmH
2
O) of
the required accessories is less than 15,0 mmH
2
O and the total
extension for each single duct is still less than 25 m.
6.13
Electrical connections
The power cable must be connected to a 230V (±10%) ~ 50 Hz
network, observing L-N polarity and the earth connection. The
network must have an omnipolar switch with category III over-
voltage, in compliance with the installation rules.
If this cable needs to be replaced, an original spare must be re-
quested from
Sime
.
Therefore only the connections of the original components as
shown in the table are needed. These are to be ordered separate-
ly from the boiler.
DESCRIPTION
CODE
Remote control HOME PLUS (open therm)
8092281
Cascade management board
8092268
Expansion card
8092272
Weekly hot-cold timer-controlled thermostat
8113509
m
CAUTION
The maintenance interventions described must ONLY
be carried out the professionally qualified personnel.
a
WARNING
Before carrying out any interventions described:
– set the main system switch to "OFF"
– close the gas valve
– make sure that no hot parts inside the appliance are
touched.
OFF
Fig. 42
To facilitate introduction of the connection wires of the optional
components into the boiler:
– remove the screws (1), pull the front panel (2) forwards and
release it from the top by lifting it
1
2
Fig. 43
– use the tabs (3) to release the control panel (4)
– bring the panel forwards and downwards until it is horizontal
4
3
3
Fig. 44