Programming Quick Reference Chart
151059
A-3
General Options
(cont.)
Display Options
(cont.)
Hold last event
Ye
s
If Y
es, LCD will display the last acknowledged event instead of
the date/time display in the auto mode. In manual mode the
display will show the oldest un
acknowledged event. See Section
5.4.2.6.
No
Communication
(cont.)
Port Functions
Com1
Unused/Automation/Printer/
Rules for Port Configuration:
Functions in Brackets [ ] appear only if “Automation” is selected
for Com1.
Functions in { } appear only if “Printer” is selected in Com1 or
Par
.
A function may be selected only once in the 3 ports (only one
printer
, only one Diag, etc.).
All ports may be configured “Unused”.
See Section 5.4.3.1.
Com2
Unused/[Auto Bkp]/[Auto Bkp
Prn]/{Print Bkp}/Diag/Printer
Par (Parallel)
Unused/[Auto Bkp]/Printer/Diag
Com Port1
Baud
38400, 19200, 9600, 7200,4800,
2400, 1200, 600, 300, 1
1
0
See Section 5.4.3.2 for details.
D (# Data Bits)
8, 7
S (# S
top bits)
1 or 2
P (Parity)
Even, Odd, No,
Port Monitor
Y
es, No
F (Flow Control)
Hdwr
, Sftwr
, None
Init S
tr
(Initialization
St
ri
n
g
)
Enter ASCII characters for the Escape command sequence
desired. For example: Set the page size or number of lines per
page for a serial printer
.
Com Port2
Same as Com1
Par Port
Edit
Init
S
tring
Enter or edit an Escape command sequence. For example: Set the
page size or number of lines per page for a printer
.
Clear Init S
tring
Automation Cfg.
Format
SK EXP
, SK9000, SIA CIS,
CAPS,
FBI I220, ADEM 685, ITIComp,
ITI Gen
See Section 5.4.3.5 for details.
Hex
Y (yes)
This feature is only available if SK 9000 automation protocol is
selected.
N (no)
Heartbeat
Y (yes)
N (no)
T
ime
(of heartbeat)
10-600 seconds
Ack timeout
1 to 120 seconds
Table A-1: Programming Quick Chart
Program Mode
Options
Choices
Choices
Choices
Choices
Comments
Summary of Contents for 9500
Page 7: ...Model 9500 Central Station Receiver Installation Operation Manual vi 151059 ...
Page 145: ...Model 9500 Central Station Receiver Installation Operation Manual 7 8 151059 ...
Page 155: ...Model 9500 Central Station Receiver Installation Operation Manual A 10 151059 ...
Page 161: ...151059 Index 4 ...