Model 9500 Central Station Receiver Installation/Operation Manual
A-4
151059
General Options
(cont.)
Communication
(cont.)
Annunciator
Configuration
Printer
Y
es or No
Y
es = will annunciate if
an event, trouble or fault condition
occurs.
No = no annunciation if an event, trouble or fault condition
occurs.
Default for all options: Y
es.
See Section 5.4.3.6.
*
L
isten In option must be set to No for UL installations.
Bkp Printer
Y
es or No
Auto Comp
Y
es or No
Bkp Auto Comp
Y
es or No
Battery
Y
es or No
Device
Y
es or No
Line Fault
Y
es or No
AC Power
Y
es or No
Buf
fer Full
Y
es or No
Listen In
Y
es or No
Call Pending
Y
es or No
Aux Relay Cfg
Options the same as Annunciator Configuration.
See Section 5.4.3.7.
*
L
isten In option must be set to No for UL installations.
System Options
Battery Backup Cfg
No Battery Bkp
No char
ging current applied to battery circuit. Receiver will not
test battery output or give trouble annunciations. Default. See
Section 5.4.4.1.
DC Bkp
No char
ging current applied to battery circuit. T
ypically used for
systems that use a UPS (uninterrupted power supply) for backup
battery power
. See Section 5.4.4.1.
Battery Bkp
Char
ging current applied to battery circuit. See Section 5.4.4.1.
Receiver ID No.
01-99
Default: 01. See Section 5.4.4.2.
Bad Data Blocks
St
ri
p
B
ad
An indicator is sent to the automation computer that indicates a
bad data block was received. Default.
See Section 5.4.4.3
Send Bad
Same as S
trip Data except the bad data block is sent with the
indicator
.
See Section 5.4.4.3
Auxiliary Relay
Normal S
tate
Of
f
Of
f= Deener
gized. Default.
On = Ener
gized
See Section 5.4.4.4.
Ener
gized
Clock Source
60 Hz
Receiver clock runs on 60Hz AC power input. See Section
5.4.4.5
50 Hz
Receiver clock runs on 50Hz AC power input. See Section
5.4.4.5.
Int
Receiver clock runs on internal crystal. Use in areas where AC
line frequency is not dependable. See Section 5.4.4.5.
Table A-1: Programming Quick Chart
Program Mode
Options
Choices
Choices
Choices
Choices
Comments
Summary of Contents for 9500
Page 7: ...Model 9500 Central Station Receiver Installation Operation Manual vi 151059 ...
Page 145: ...Model 9500 Central Station Receiver Installation Operation Manual 7 8 151059 ...
Page 155: ...Model 9500 Central Station Receiver Installation Operation Manual A 10 151059 ...
Page 161: ...151059 Index 4 ...