MapIT G2 Hardware Installation Training Manual
Confidential – June 2014
17
Note
: If the redundant daisy chain is used, the two daisy chained links
must be served from the same MCP or DCP. Do not attempt to span the
redundant link between different MCPs or DCPs.
2. Enclosure Grounding
– A ground lug is provided on the rear of the SFE
to ground it to the rack or telecommunications ground. The SFE must be
properly grounded for the system to function properly
3. SFE vs. SMTP
– The SFE is use for direct termination LC, fusion splicing
and LC trunks. The SMTP is prepopulated with LC to MTP cassettes.
Use the SMTP when using MTP fiber trunks
Expanded View of SMTP Enclosure