6 – 4
6.2
Charging the storage spring
Charging manually
F
Handle force
n
Number of strokes
(1)
Spring charged
Charging by motor-operated mechanism
The motor-operated mechanism starts automatically
after applying control voltage. The motor is automat-
ically switched-off at the end of the charging opera-
tion.
The motor will re-engage immediately following
spring discharge (closing operation).
Installing the motor-operated mechanism (page 13-1)
6.2
Federspeicher spannen
Spannen per Hand
F
Betätigungskraft
n
Anzahl der Hübe
(1)
Feder ist gespannt
Spannen durch Motorantrieb
Motorantrieb startet automatisch nach Anlegen der
Steuerspannung. Am Ende des Spannvorgangs
schaltet der Motor automatisch ab.
Unmittelbar nach dem Entspannen des Federspei-
chers wird der Motor erneut eingeschaltet und damit
die Feder wieder gespannt (nach einem Einschalt-
vorgang).
Nachrüsten des Motorantriebs (Seite 13-1)
WARNUNG
WARNING
Schwere Ausrüstung!
Kann Personen- und Sachschäden verursachen.
Einen Leistungsschalter vor dem Spannen des Federspeichers
unbedingt in geeigneter Weise abstützen (z. B. bei Wartungs-
arbeiten auf der Werkbank).
Heavy equipment!
May result in serious injury and property damage.
Secure the circuit breaker before charging it manually (e. g.
during service on the work bench).
ACHTUNG
NOTICE
Zum Spannen des Federspeichers den Handhebel vollständig
umfassen und jeden Hub gleichmäßig und vollständig bis zum
Anschlag ausführen. Der 9. Hub ist genauso weit zu betäti-
gen, wie die ersten acht Hübe, obwohl die Betätigungskraft
deutlich zunimmt. Ist der Federspeicher vollständig gespannt,
lässt sich der Handhebel ohne Widerstand bewegen.
For charging the spring mechanism completely grab the
handle and steadlily execute each stroke as far as it will go.
Execute the 9th stroke as far as the first eight strokes,
although the handle force will increase significantly. When
fully charged, further strokes would feel like idle operations.
9 x
1
2
3
4
5
6
7
8
9
10
n
F
0727
(1)
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......