9 – 69
- direct sensing of ground return, using a 1200 A : 1 A iron
core sensor
Input current carrying capacity of the ground-fault protection
module:
- max. 1 A continuously
- max. 5 A for 0.5
sec.
.
Alarm and trip signals can be transmitted via the
c
and
the PROFIBUS-DP.
Module GFM A 745
- Alarm only, circuit breaker is not tripped
- Changeover switch for ground-fault detection mode only acces-
sible when either the module or the trip unit is removed.
Module GFM AT 745
- Ground-fault protection by tripping the circuit breaker and alarm
signaling
- Changeover switch for ground-fault detection mode only acces-
sible when either the module or the trip unit is removed.
Module GFM A 755 - 776
- Alarm only, circuit breaker is not tripped
- Module programmable via:
- the graphical display (ETU776)
- direkter Messung des Erdschlussstromrs mit einem sepa-
raten Erdschlusswandler 1200 A : 1 A.
Belastbarkeit des Eingangs der Erdschlussschutzmodule:
- max. 1 A dauernd
- max. 5 A für 0,5 s.
Alarm- und Ausgelöstmeldungen können über den
c
,
PROFIBUS-DP und den MODBUS ausgegeben werden.
Modul GFM A 745
- nur Alarmmeldung, Leistungsschalter wird nicht ausgelöst
- Umschalter Erdschlusserfassung nur bei ausgebautem Modul
oder ausgebautem Überstromauslöser zugänglich
Modul GFM AT 745
- Erdschlussschutz durch Auslösung des Leistungsschalters und
Alarmmeldung
- Umschalter Erdschlusserfassung nur bei ausgebautem Modul
oder ausgebautem Überstromauslöser zugänglich
Modul GFM A 755 - 776
- nur Alarmmeldung, Leistungsschalter wird nicht ausgelöst
- Modul parametrierbar über:
- das Grafikdisplay (ETU776)
Rotary coding switch ground fault
Drehkodierschalter Einstellwert
alarm setting
Erdschlussalarm
Ground fault alarm indicator
Anzeige Erdschlussalarm
Rotary coding switch ground fault
Drehkodierschalter Erdschlussschutz
delay setting t
g
/ I
2
t
g
Verzögerung t
g
/ I
2
t
g
Changeover switch ground fault
detection mode
Umschalter Erdschlusserfassung
Rotary coding switch ground fault
Drehkodierschalter Einstellwert
pickup setting
Erdschlussschutz
Rotary coding switch ground fault
Drehkodierschalter Einstellwert
alarm setting
Erdschlussalarm
Indicators
Anzeigen
Ground fault alarm
Erdschlussalarm
Ground fault tripped
Erdschluss ausgelöst
Rotary coding switch ground fault
Drehkodierschalter Erdschlussschutz
delay setting t
g
/ I
2
t
g
Verzögerung t
g
/ I
2
t
g
Changeover switch ground fault
detection mode
Umschalter Erdschlusserfassung
Ground fault detection mode
Erdschlusserfassung
Areas to record
Felder zum Notieren
der Einstellwerte
protective settings
Areas to record
Felder zum Notieren
der Einstellwerte
protective settings
Ground fault alarm indicator
Anzeige Erdschlussalarm
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......
Page 361: ......