6 – 13
6.9
Troubleshooting
1)
Safety
feature!
This remedy action amounts to a reversal (disabling) of a safety precaution
installed earlier. Please ensure that such disabling is now permissible / authori-
zed!
Fixed-moun-
ted breaker
Draw-out
breaker
Disturbance
Possible Cause(s)
Remedy
X
X
Circuit breaker cannot be
closed.
Circuit breaker
not
ready to
close.
Ready-to-close indicator
shows:
1.
Spring not charged
Charge spring
X
X
2.
Undervoltage release not ener-
gized.
Energize undervoltage release
X
X
3.
Mechanical open fuse lock-out
effective
For fused circuit breakers:
Replace defective fuses and press
reset button
X
X
4.
Electrical closing interlock effective
Shut off control voltage for interlocking
1)
X
X
5.
"
Safety OPEN
" locked with cylin-
der lock
(accessories)
Unlock
1)
X
X
6.
"
Safety OPEN
" locked with pad-
locks
(accessories)
Remove padlocks
1)
X
X
7.
"OPEN" button locked off
(accessories)
Unlock the "OPEN" button
1)
X
X
8.
"EMERGENCY OPEN" button
engaged in
operating position
(accessories)
Release "EMERGENCY OPEN" but-
ton
1)
by
rotating it
X
X
9.
Lockout effective against closing
when cubicle door is open (acces-
sories)
Close cubicle door
X
X
10. Mutual mechanical circuit breaker
interlocks effective (accessories)
Open second circuit breaker or rack
into disconnected
position
1)
X
X
11. Electronic
trip unit
missing or
incorrectly installed
Install electronic
trip unit
properly
X
X
12. Shunt trip energized
Deenergize shunt trip
X
X
13. Close coil energized
Closing coil has to be deenergized
shortly for reclosing
X
14. Racking handle withdrawn
Rack circuit breaker into disconnected,
test or connect position, unlatch crank
and push crank fully in
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......
Page 361: ......