10 – 7
10.4.3
Function test
Then
- Install trip unit
q
- Install front panel
q
10.4.4
Updating the options label
X7.12
X7.14
X7.13
S24
X7.12
X7.14
X7.13
S24
10.4.3
Funktionstest
Anschließend
- Überstromauslöser einbauen
q
- Bedienpult anbauen
q
10.4.4
Ausstattungsschild aktualisieren
1
2
3
Hinweis
NOTICE
Nach dem Einbau zusätzlicher elektrischer Komponenten fol-
gende Angaben mit einem weißen, wisch- und wasserfesten
Stift durch ankreuzen aktualisieren.
After installing additional electrical components, add the follo-
wing data and mark with a “x”, using a black or blue indelible
ink pen!
Voltage
Spannung
Catalog No.
Bestell-Nr.
Remote bell alarm reset solenoid
Fern-Rücksetzmagnet
24 V DC
WLRSET24
48 V DC
WLRSET48
110 - 125 V AC / DC
WLRSET120
208 - 250 V AC / DC
WLRSET240
S24
0053-06_u
F7
S13
X8.13
X8.14
S24
X7.13
X7.14
X7.12
Siemens Energy & Automation, Inc., Grand Prairie, TX 75050, USA
Charging Motor
Remote Close Coil
X5-2 (+)
X5-1 (-)
X6-7 (+)
X6-8 (-)
240
250
VAC
VDC
120
125
VAC
VDC
240
250
VAC
VDC
120
125
VAC
VDC
VAC
VDC
120
125
VAC
VDC
1st Shunt Trip
UVR
2nd Shunt Trip
Remote Reset
X6-13 (-)
X6-14 (+)
X5-11 (-)
X5-12 (+)
X9-1 (-)
X9-2 (+)
X8-13 (-)
X8-14 (+)
Ready to Close Switch
X6-5
X6-6
240 VAC
4 A
240 VAC
1st Shunt Trip Switch
X9-7
X9-8
240 VAC
UVR Switch
X9-10
X9-11
52a
1st Aux. SW.
52b
X6-3
X6-4
X6-11
X6-12
X6-1
X6-2
X6-9
X6-10
X5-5
X5-6
X5-9
X5-10
X5-3
X5-4
X5-7
X5-8
52a
2nd Aux. SW.
52b
240 VAC ,
Bell Alarm
240 VAC
5 A
X9-13
X9-14
X9-12
3 A
3 A
Assembled in USA
10 A / 125 VDC ,
0.5 A / 24 VDC ,
3A
0131_nu
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......
Page 361: ......