25 – 9
WL Circuit Breaker
Function Overview of the Electronic Trip Units
Basic Functions
ETU748
ETU755
ETU776
Long-time overcurrent protection
✔
✔
✔
Function can be switched ON/OFF
–
–
–
Setting range
IR = In x …
0.4, 0.45, 0.5, 0.55,
0.4 … 1 (step: 1A)
0.4 … 1 (step: 1A)
0.6, 0.65, 0.7, 0.8,
0.9, 1
Switch-selectable overload protection
(
I2t or I4t dependent function)
✔
✔
(via communications)
✔
Setting range of time delay class
tR at I
2t
(seconds)
2, 3.5, 5.5, 8, 10,
2 … 30 (step: 0.1s)
2 … 30 (step: 0.1s)
14, 17, 21, 25, 30
Setting range of time delay
tR at I
4t
(seconds)
1, 2, 3, 4, 5
1 … 5 (step: 0.1s)
1 … 5 (step: 0.1s)
Thermal memory
✔
(via slide switch)
✔
(on/off via communications)
✔
(on/off via key pad
or communications)
Phase loss sensitivity
at
tsd=20ms (M)
✔
(on/off via communications)
✔
(on/off via key pad
or communications)
N-conductor protection
–
✔
✔
Function can be switched ON/OFF
–
✔
(via slide switch)
✔
(via slide switch)
N-conductor setting range
IN = In x …
–
1
0.5 … 1
Short-time delayed overcurrent protection
✔
✔
✔
Function can be switched ON/OFF
✔
(via rotary switch)
✔
(via communications)
✔
(via key pad or communications)
Setting range
Isd = In x …
1.25, 1.5, 2, 2.5,
1.25 … 0.8 x Icw = max
1.25 … 0.8 x Icw = max
3, 4, 6, 8, 10, 12
(step: 10A)
(step: 10A)
Setting range of time delay
tsd, fixed
(seconds)
M, 0.1, 0.2, 0.3, 0.4
M, 0.08 … 0.4, OFF (step: 0.001s)
M, 0.08 … 0.4, OFF (step: 0.001s)
Switch-selectable short -time delay
short-circuit protection
(
I2t dependent function)
✔
(via rotary switch)
✔
(via communications)
✔
(via key pad or communications)
Setting range of time delay
tsd at I
2t
(seconds)
0.1, 0.2, 0.3, 0.4
0.1 … 0.4 (step: 0.001s)
0.1 … 0.4 (step: 0.001s)
Zone Selective Interlocking (ZSI) function
per CubicleBUS module
per CubicleBUS module
per CubicleBUS module
Instantaneous overcurrent protection
✔
✔
✔
Function can be switched ON/OFF,
Extended Instantaneous Protection
is enabled when OFF
–
✔
(via communications)
✔
(via key pad or communications)
Setting range
Ii = In x …
–
I
i
=
I
cw
= EIP
1.5 x
I
n
… 0.8 x
I
cs
= max, OFF=
I
cw
=EIP
1.5 x
I
n
… 0.8 x
I
cs
= max, OFF=
I
cw
=EIP
Ground fault protection
O
(field installable module)
O
(field installable module)
O
(field installable module)
Trip and alarm function
✔
✔
(via communications)
✔
(via key pad or communications)
Detection of the ground fault current
by residual summing method
✔
✔
✔
Detection of the ground fault current
by direct summing method
✔
✔
✔
Setting range of the
Ig for trip
A, B, C, D, E
A … E (step: 1A)
A … E (step: 1A)
Setting range of the
Ig for alarm
A, B, C, D, E
A … E (step: 1A)-
A … E (step: 1A)
Setting range of the time delay
tg
(seconds)
0.1, 0.2, 0.3, 0.4, 0.5
0.1 … 0.5 (step: 0.001s)
0.1 … 0.5 (step: 0.001s)
Switch-selectable
ground fault protection
(
I2t / fixed)
✔
✔
✔
Setting range time delay
tg at I
2t
0.1, 0.2, 0.3, 0.4, 0.5
0.1 … 0.5 (step: 0.001s)
0.1 … 0.5 (step: 0.001s)
ZSI ground function
per CubicleBUS module
per CubicleBUS module
per CubicleBUS module
✔
available
–
not available
O
optional
L
N
S
I
G
Extended Instantaneous Protection (EIP) allows the WL breaker to be applied at the withstand rating of
the breaker with minus 0% tolerance; that means no instantaneous override whatsoever. EIP further
enables the circuit breaker to be applied up to the full instantaneous rating of the breaker on systems
where the available fault current exceeds the withstand rating.
Ground Fault Module cannot be removed after installation.
1
2
Notes:
M
= Motor protection setting (20 ms)
Communications
= Setting the parameters of the trip unit
via the Breaker Data Adapter, MODBUS, or PROFIBUS
Key pad
= Direct input at the trip unit
In
2
1
1
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......
Page 361: ......