9 – 90
MODBUS Functionality
Transmission Protocol
The COM16 module only operates in the RTU transmission mode.
ASCII transmission mode is not supported.
Overview of the Supported Functions
The COM16 module provides the following MODBUS function
codes to access the data contained in the 3WL circuit breaker.
More information is available in the "WL Trip Unit, MODBUS Com-
munication and Electronic Accessories Application Guide".
MODBUS Communication settings
For a MODBUS communication the following parameters have to be
set in the COM16 module: baud rate, serial line configuration and
the MODBUS address.
Further information is given in the manual "MODBUS Profile for WL
Circuit Breaker".
MODBUS Slave Address
The MODBUS communication address range of the COM16
module is 1 through 126.
MODBUS address 0 is used as a broadcast address on MODBUS
systems.
MODBUS address 0xF1(hex) is defined as a broadcast address for
the COM16 modules.
The MODBUS slave address is assigned to data point 5 and may be
changed by writing a new address value to byte 5 in data set 160. If
the COM16 module receives an invalid slave address value, the
invalid value will be ignored.
Baud Rate
Baud rate settings of 1200, 2400, 4800, 9600 and 19200 are sup-
ported. 19200 baud is the default setting. The baud rate is assigned
to data point 427 and may be changed by writing a new baud rate
MODBUS Funktionalität
Transmission Protokoll
Das COM16-Modul unterstützt des RTU-Mode für die MOD-
BUS-Übertragung. Der ASCII-Mode wird nicht unterstützt.
Übersicht über die unterstützten Funktionen
Das COM16-Modul stellt folgende MODBUS-Funktionen für den
Zugriff auf die Daten des 3WL Leistungsschalters zur Verfügung.
Weitere Informationen sind im Handbuch „WL Trip Unit, MODBUS
Communication and Electronic Accessories Application Guide" ent-
halten.
MODBUS Kommunikationseinstellungen
Für die MODBUS-Kommunikation müssen die folgenden Einstellun-
gen im COM16-Modul vorgenommen werden: Konfiguration der
seriellen Übertragung, MODBUS-Adresse.
Weitere Informationen sind im Handbuch "MODBUS Profile for 3WL
Circuit Breaker" enthalten.
MODBUS Slave Addresse
Der Bereich für die MODBUS-Kommunikationsadresse des
COM16-Moduls ist von 1 bis 126.
Die MODBUS-Adresse 0 wird als Broadcast-Adresse im MOD-
BUS-System verwendet.
Die MODBUS-Adresse 0xF1 (hex) ist als Broadcast-Adresse für
COM16-Module definiert.
Die MODBUS-Adresse ist dem Datenpunkt 5 zugeordnet und kann
durch Schreiben auf das Byte 5 im Datensatz 160 geändert werden.
Wenn das COM16-Modul einen ungültigen Wert für die MOD-
BUS-Adresse empfängt, dann wird der ungültige Wert ignoriert.
Baud Rate
Die Baudraten 1200, 2400, 4800, 9600 und 19200 werden unter-
stützt. 19200 Baud ist die Liefereinstellung. Die Baudrate ist dem
Datenpunkt 427 zugeordnet und kann durch Schreiben auf das
FC
Name
Description
02:
Read Input Status
Reads the state of the bits in the Status Register
01:
Read Coil Status
Reads the state of multiple Control bits and Extra flags
05:
Force Single Coil
Sets the state of a single Control bit or Extra flag
15:
Force Multiple Coils
Sets the state of multiple Control bits and Extra flags
04:
Read Input Registers
Reads the Basic Data Registers. Three Basic Types (1, 2 and 3) are
supported.
03:
Read Holding Registers
Reads a complete data set.
16:
Preset Holding Registers
Writes a complete data set.
07:
Read Exception Status
Reads the state of eight Exception Status bits
08:
Diagnostic
Function provides a method for checking the communication between
the master and the slave
11:
Fetch Communication Event
Counter
Returns a status word and an event count from the communications
event counter
12:
Fetch Communication Event Log
Returns a status word, event count, message count, and a field of
event bytes
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......
Page 361: ......