Status Register
The Status Register provides 3WL status information to the MOD-
BUS master. The Status Register is accessed using the following
functions:
- 02 Read Input StatusReads the Status Register
- 04 Read Input RegistersReads the Status Register and Basic
data
Bit Number
3WL
0, 1
Circuit Breaker Position
00 = disconnect
01 = connect
10 = Test
11 = breaker present
2, 3
Circuit Breaker Status
00 = not ready
01 = Breaker Off
10 = Breaker On
11 = Breaker Trip
4
Circuit Breaker Ready to Close
5
Under voltage release
6
Spring Charged
7
Overload Warning
8
Setpoints active
9
Warning active
10
MODBUS Write enable
11
User Input
12, 13, 14
Trip
000 = no trip
001 = long time trip
010 = instantaneous trip
011 = short time trip
100 = ground fault trip
101 = extended trip
110 = neutral trip
15
Load shedding
Status Register
Die Status Register liefern die 3WL Statusinformationen an den
MODBUS-Master. Der Zugriff auf die Status-Register erfolgt über
die folgenden Funktionen:
- 02 Read Input StatusReads the Status Register
- 04 Read Input RegistersReads the Status Register and Basic
data
Bit Number
3WL
0, 1
Position des Leistungsschalters
00 = Trennstellung
01 = Betriebsstellung
10 = Teststellung
11 = Schalter anwesend
2, 3
Status des Leistungsschalters
00 = nicht einschaltbereit
01 = Schalter ausgeschaltet
10 = Schalter eingeschaltet
11 = Ausgelöst
4
Leistungsschalter ist einschaltbereit
5
Unterspannungsauslösung
6
Federspeicher gespannt
7
Überlastwarnung
8
Setpoint aktiv
9
Warnmeldung aktiv
10
MODBUS "Write Enable"-Eingang aktiv
11
Benutzereingang
12, 13, 14
Auslösung
000 = keine Auslösung
001 = Überlastauslösung
010 = Unverzögerte Kurschlussauslösung
011 = Kurzzeitverzögerte Kurzschlussauslösung
100 = Erdschlussauslösung
101 = Auslösung wg. erweiterter Schutzfunktion
110 = N-Leiter-Auslösung
15
Lastabwurf
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......
Page 361: ......