9 – 24
Ground-fault tripping – G-tripping
If the trip unit is equipped with a ground-fault protection module,
loads can be protected against unpermissibly high ground-fault cur-
rents.
The trip unit ETU727 is equipped with a ground-fault protection
module as standard, whereas the trip units ETU745 - 776 can be
equipped with it optionally.
q
Ground-fault protection modules (page 9-68)
The pickup I
g
, together with the setting for the time-delay t
g
, deter-
mines the shutdown of ground-fault currents.
Some trip units can be switched over to an I
2
t-characteristic..
q
Neutral conductor protection - N-tripping
The trip units ETU727 ... 776 also make it possible to protect the
neutral conductor against overload. This requires a current trans-
former for the neutral conductor, which can be field installed.
q
For tripping, the same long time delay t
R
applies as for overload trip-
ping.
Current Settings for I
g
Frame size
I & II
III
A
100 A
400 A
B
300 A
600 A
C
600 A
800 A
D
900 A
1000 A
E
1200 A
1200 A
Settings for t
g
ETU727 - 748
t
g
= 0.1 / 0.2 / 0.3 / 0.4 / 0.5
sec.
ETU755 - 776
t
g
= 0.1 - 0.5
sec.
Current Settings for I
N
ETU727
I
N
= I
n
; OFF
ETU745 - 748
I
N
= (0.5 / 1.0) × I
n
; OFF
ETU755 - 776
I
N
= (0.5 - 2.0) × I
n
; OFF
Erdschlussauslösung – G-Auslösung
Ist der Überstromauslöser mit einem Erdschlussschutzmodul aus-
gestattet, können Verbraucher vor unzulässig hohen Erdschluss-
strömen geschützt werden.
Der Überstromauslöser ETU727 verfügt standardmäßig über einen
Erdschlussschutz, während die Überstromauslöser ETU745 - 776
optional damit ausgerüstet werden können.
q
Erdschlussschutzmodule (Seite 9-68)
Der Ansprechwert I
g
legt zusammen mit der Einstellung der Verzö-
gerungszeit t
g
die Abschaltung von Erdschlussfehlern fest.
Für einige Überstromauslöser besteht die Möglichkeit, auf eine
I
2
t-Charakteristik umzuschalten.
q
Neutralleiterschutz – N-Auslösung
Die Überstromauslöser ETU727 … 776 bieten die Möglichkeit, auch
den Neutralleiter vor Überlast zu schützen. Dazu ist ein Stromwand-
ler für den Neutralleiter erforderlich, der ggf. nachgerüstet werden
kann.
q
Für die Auslösung gilt der gleiche Trägheitsgrad t
R
, wie für die Über-
lastauslösung.
Einstellwerte für I
g
Baugröße
I & II
III
A
100 A
400 A
B
300 A
600 A
C
600 A
800 A
D
900 A
1000 A
E
1200 A
1200 A
Einstellwerte für t
g
ETU727 - 748
t
g
= 0,1 / 0,2 / 0,3 / 0,4 / 0,5 s
ETU755 - 776
t
g
= 0,1 - 0,5 s
Einstellwerte für I
N
ETU727
I
N
= I
n
; OFF
ETU745 - 748
I
N
= (0,5 / 1,0) × I
n
; OFF
ETU755 - 776
I
N
= (0,5 - 2,0) × I
n
; OFF
VORSICHT
CAUTION
Einstellwerte I
N
> 1 x I
n
nur bei entsprechender
Dimensionierung des N-Leiters verwenden!
Setting I
N
> 1 x I
n
may be used only if the N-conduc-
tor has been designed to carry this current.
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......
Page 361: ......