9 – 68
Remove
9.1.12
Ground-fault protection modules
Various trip units can be optionally equipped with ground-fault pro-
tection modules.
The ground fault protection of the module GFM AT 745-748 and the
ETU727 meet the conditions for „Groud fault protection for equip-
ment“ according UL 489, the calibration meets UL 1053.
If the current setting is exceeded, this causes an alarm or - at the
same time - the tripping of the trip unit, depending on the version of
the ground-fault protection module.
q
The following variations are possible:
The ground fault can be optionally detected as follows:
- Residual of phase currents in three phase systems or
residual of phase currents and neutral current if neutral
pole sensor is used
Trip unit
Ground-fault protection module
ETU745 - 748
GFM A 745-748
GFM AT 745-748
ETU755 - 776
GFM A 755-776
GFM AT 755-776
2
3
Entnehmen
9.1.12
Erdschlussschutzmodule
Für verschiedene Überstromauslöser stehen optional Erdschluss-
schutzmodule zur Verfügung.
Der Erdschlussschutz des Moduls GFM AT 745-748 und der
ETU727 erfüllt die Bedingungen „Erdschlussschutz für Anlagen“
nach UL 489, seine Kalibrierung entspricht der UL 1053.
Das Überschreiten des Einstellwertes führt je nach Ausführung des
Erdschlussschutzmoduls nur zur Ausgabe einer Meldung oder
gleichzeitig auch zum Auslösen des Überstromauslösers.
q
Folgende Gerätekombinationen sind möglich:
Die Erdschlusserfassung kann wahlweise erfolgen mittels:
- vektorieller Summenbildung der Phasenströme oder vek-
torieller Summenbildung der Phasenströme und des Neu-
tralleiterstromes, wenn ein Neutralwandler vorhanden
2000 A
WLRP2000
2500 A
WLRP2500
3000 A
WLRP3000
3200 A
WLRP3200
4000 A
WLRP4000
5000 A
WLRP5000
VORSICHT
CAUTION
Das Bemessungsstrommodul darf nur unter folgenden Bedingun-
gen gezogen werden:
- der Einschubschalter befindet sich in der Trennposition
oder
- der Überstromauslöser ist ausgebaut.
Remove rating plug only when the circuit breaker is in the open
position.
If the rating plug is removed with the circuit breaker is in the clo-
sed position, the trip unit can trip the circuit breaker unintentio-
nally.
Überstromauslöser
Erdschlussschutzmodul
ETU745 - 748
GFM A 745-748
GFM AT 745-748
ETU755 - 776
GFM A 755-776
GFM AT 755-776
Frame size
Baugröße
Rating plug
Bemessungstrom-modul
Catalog No.
Bestell-Nr.
I
II
III
AUS / OPEN
1
Summary of Contents for WL Series
Page 64: ...7 2 Horizontalanschlüsse 0733_nu top view Horizontal connectors ...
Page 65: ...7 3 Vertikalanschlüsse 0734_nu top view rear view Rear vertical connectors ...
Page 66: ...7 4 Frontanschlüsse 0736_nu front view top view Front connectors ...
Page 68: ...7 6 7 2 Baugröße II Festeinbau 0494 3_nu 7 2 Frame size II fixed mounted version ...
Page 69: ...7 7 C class always 0494 5_nu top view rear view ...
Page 70: ...7 8 0738_nu LH side view front view ...
Page 72: ...7 10 0495 2_nu top view top view ...
Page 73: ...7 11 0495 3_nu top view rear view ...
Page 74: ...7 12 0739_nu LH side view front view ...
Page 76: ...7 14 Baugröße II III 0496_nu Frame size II III ...
Page 77: ...7 15 7 5 Baugröße I Einschubausführung 0745_nu 7 5 Frame size I draw out version ...
Page 78: ...7 16 0746_nu rear view top view ...
Page 79: ...7 17 0747_nu bottom view ...
Page 80: ...7 18 0748_nu ...
Page 81: ...7 19 0749_nu ...
Page 82: ...7 20 7 6 Baugröße II Einschubausführung 0490 1_ul 7 6 Frame size II draw out version ...
Page 86: ...7 24 7 7 Baugröße III Einschubausführung 7 7 Frame size III draw out version ...
Page 87: ...7 25 ...
Page 88: ...7 26 ...
Page 111: ...9 11 I Auslösung Erdschlussauslösung I tripping Ground fault tripping ...
Page 360: ......
Page 361: ......