Fire Safety & Security Products
Building Technologies
1583_o_en_−−_6
111
08.2005
6.5
Control line for alarm devices (horn)
Pluggable terminal block
K3/K13/K23
Horn 2 or 4 or 6
monitored
Horn 1 or 3 or 5
monitored
F5
24V
max.0,5A
3
2
1
+
−
+
−
4
F6
0,5A/F
0,5A/F
24V
max.0,5A
BELL
master board
K3M010
K3G050
V
W
R
Q
–
+
–
+
L
L
DC1192
SynoLOOP
24V
DC
+
–
24V
max.2A
3k
¼
W (1%)
1) only limited power available at control unit
(possibly use of external power supply)
1)
+
–
FC330A / K3M010 / K3G050
12k
/
½
W
3,01k
/
½
W (1%)
12k
/
½
W
3,01k
/
½
W (1%)
end of line
on K3X020
end of line
on K3M010/K3G050
Function
Sounder control lines
on K3X020/030, K3M010, K3G050
on DC1192
1)
Max. number control lines
K3X020
2 control lines
K3M010
2 optional contr. lines
K3G050
2 optional contr. lines
DC1192
1 control line
per SynoLOOP
..40 DC1192
(with external power supply)
Application
to drive alarm sounders, sirens with a
supply voltage of 24..29V
DC
to drive alarm sounders, sirens with a
supply voltage of 24..29V
DC
Operating facility
− disabling
− manual activation for testing from
control unit
yes
yes
yes
no
State ‘active’
− initiation criterion
− voltage applied on sounder circuit
− max. current to power sounders
− duration of state active
− active mode
− renewed active with new alarm
− renewed active with RESOUND
5)
− also activated via input EVAC
alarm
24..29V
DC
(reversed polarity)
..500mA
until ACK
continuous or pulsating
yes
yes
yes
programmed trigger
18..32V
DC
(reversed polarity)
2)
..2A
until ACK or INACTIVE
continuous or pulsating
yes
no
no
Programming facility
− activation trigger
− selectable pulsating rate
− to be assigned to conTrol zone
ALARM any zone
variable rate 0.3 .. 2sec / 0.3 ..2sec
no
ALARM any or specific zone(s)
3)
fixed rate 1sec / 1sec
4)
yes
Line monitoring
− monitoring voltage
− end-of-line unit
11..13V
DC
on K3X020/030: resistor 3,01k
Ω
½
W (1%)
on K3M010/K3G050: resistor 12k
Ω
½
W
18..22V
DC
resistor 3k
Ω
¼
W (1%)
Special requirements
− in compliance with VdS 2489
− pulsating rate synchronised
− sounders shall only draw current in
state ‘active’ (reversed polarity)
yes, via optional M3C080
yes
yes (possibly via diode)
no
no
yes (possibly via diode)
1) details about DC1192 see detector manual
2) depending on the power input of the DC1192
3) also other triggers than ALARM possible
4) sound mode ‘continuous’ or ‘pulsating’ selectable via DIP−switch inside DC1192
5) RESOUND = reactivation alarm horns after ACKNOWLEDGE (renewed pressing key ACK)