Background information
6.1
Power supply
6.1.1
Quiescent current table
Basic information to determine the capacity of the emergency power battery in relation
with the used hardware.
Module
Quiescent current at 24V
DC
during mains failure
Additional current with alarm condition
K3X030
100mA
1 loop with 1 connected detector
all monitored control lines terminated
state FAULT acknowledged
backlight of LCD not lit (after timeout)
+ 9mA
per activated control line
2)
+ 8mA
if buzzer is activated
+ 40mA
if backlight of LCD is lit
K3X020
128mA
2 loops each with 1 connected detector
1)
all monitored control lines terminated
state FAULT acknowledged
backlight of LCD not lit (after timeout)
+ 9mA
per activated control line
2)
+ 8mA
if buzzer is activated
+ 40mA
if backlight of LCD is lit
K3X020
and
K3M030
130mA
4 loops each with 1 connected detector
1)
all monitored control lines terminated
state FAULT acknowledged
backlight of LCD not lit (after timeout)
+ 9mA
per activated control line
2)
+ 8mA
if buzzer is activated
+ 40mA
if backlight of LCD is lit
detector
0.2mA
per connected ’AnalogPLUS’ device
+ 0mA
K3M010
12mA
without detectors, but lines terminated
25mA
with 4 fully loaded lines
+ 40mA
per line in alarm
+ 9mA
per monitored control line
2)
K3M020
34mA
without detectors, but lines terminated
72mA
with 12 fully loaded lines
+ 40mA
per line in alarm
K3L070
12mA
+ 40mA
if ÜE (HM) is active
K3L100
17mA
+ 6mA
per activated driver outputs
K3G050
20mA
+ 9mA
per activated control line
2)
K3I080
10mA
+ 0mA
K3I090
50mA
+ 0mA
Z3B171
0mA
+ 27mA
per relay activated
B3R080
2mA
all LEDs inactive
+ 6mA
per LED activated
B2Q191
33mA
+ 900mA
during printing
Z3I1000 3)
8mA
4)
+ 0mA
Z3I1020
0mA
5)
+ 0mA
B3Q580
20mA
6)
+ 160mA
B3Q59x
18mA
6)
+ 167mA
K3I050
15mA
6)
+ 4mA
per activated LED-output
K3I110
24mA
6)
+ 10mA
per activated relay (onboard LED inactive = 7.3mA)
K3R072
40mA
6)
+ 2mA
per activated LED on F50F410
+ 0mA
if K3G060 is connected, details see K3G060
B3R051
40mA
6)
+ 2mA
per activated relay
K3G060
3mA
6)
+ 6mA
per activated relay
typical values at 24V
Remarks:
1) Each loop without any devices consumes additional 14mA.
2) Without external load (sounders etc.).
3) Additional power supply consisting of converter B2F040 and monitoring card M3P140.
4) The standard power supply of the FC330A−x can only supply max. 10 B3Q580 or max. 8 B3Q59x (due to the high alarm current).
If a higher Number is needed use the additional power supply Z3I1000 (Z3I1000 = M3P140).
5) Switching unit to be used to process 2 battery packs.
6) For details see document e1923.