Quick commission procedure FC330A
1
I check detector network
− insert commissioning plug CDM320
or DZB1191 into each detector
base and test the loop
− requires a completed and correctly
wired detector network
− choose detector typ according to
’field device list’
a) open knockouts where required
b) mount cabinet
c) insert EPROM + inscription stripes
d) connect de control lines
e) remove mains fuse
f)
connect mains supply line
g) position battery (do not connect)
OP320A
OH320A
HI320A
Requirements:
− System ready ?
− Mains voltage available ?
− Field device list complete ?
− Safety instructions followed ?
if yes
1) insert mains fuses + connect battery
2) select option
’2. autom. config
’
3) wait for readout on display
4) compare number of ’planned’ with number
of ’seen’ devices
5) if equal
system runs on default
proceed according to manual
if not
complete or correct detector network
2
3
4
Startup system for installation test
Mount + prepare panel
Insert detectors if network is ok
MT320A
MT320A
CDM320
CDM320
INITIATION mode: 1. restart
2. autom. config.
c)
d)
e)
g)
f)
configuration READ: ## LON−dev.
###### #:### DEVICES ###### #:### DEVICES
###### #:### DEVICES ###### #:### DEVICES
> press key ’F1’ to CONTINUE