Fire Safety & Security Products
Building Technologies
1583_o_en_−−_5
79
08.2005
5.9.1
Functions on level CONFIGURATION 1. line
Submenu 4. addressable line
to define line type, number of devices, link devices
to define device parameters
to define zone parameters
to define element parameters
to link conventional lines to zone (if available)
to check configuration before exit the programming mode
to delete all user data
to read actual line configuration as installed
to define control outputs
CONFIGURATION 1. line
(c) 2. device
3. zone
4. element
5. line ’collective’
6. CHECK configuration
7. CLEAR configuration
8. AUTOM. configuration
9. CONFIG ConTrol−ZONES
Functions as displayed
Purpose
Selectable options/Remarks
# lines defined 1. first line number
(c.1) 2. configure
− to define where the line numbering has to
start (OFFSET)
− only to be changed if the lines do not have to
start with number 1..
default = 1
(starting with number 1)
line ##: 1. type ######
(c.1.2) 2. devices ###
3. link devices
4. unlink devices
to define: − line type
− number of devices
− allocation device -> zone
− allocation device -> conTrol zone
line ##: 1. type ######
LOOP
STUB
NONE
– to define line type
LOOP
= line used as ’loop line’
STUB
= line used as ‘stub-line’
NONE
= line not used
(c.1.2) 2. devices ###
(c.1.2.2) 1. ADD device
2. DELETE device
– to add or to remove devices at the selected
position
– max. 32 per
STUB
or 128 per
LOOP
Note: all devices located after the deleted device(s)
are ‘shifted’ and all allocations are kept
enter number of new devices and
position within the line
enter position within the line num-
ber of devices to be deleted
3. link devices
LINK device line ## device ###
– to link devices to the zone
Note: If during system startup function ‘auto. configura-
tion’ is selected, then each device is automati-
cally allocated to separate zone (with ascending
number)
normally all devices per room are
to be linked to a common zone
4. unlink devices
UNLINK device line ## device ###
– to unlink devices from the allocated zone