Fire Safety & Security Products
Building Technologies
1583_o_en_−−_5
87
08.2005
5.12.1
Functions on level 4. element
Submenu 4. addressable line
to define line type, number of devices, link devices
to define device parameters
to define zone parameters
to define element parameters
to link conventional lines to zone (if available)
to check configuration before exit the programming mode
to delete all user data
to read actual line configuration as installed
to define control outputs
CONFIGURATION 1. line
(c) 2. device
3. zone
4. element
5. line ’collective’
6. CHECK configuration
7. CLEAR configuration
8. AUTOM. configuration
9. CONFIG ConTrol−ZONES
These parameter settings are done on level (c) 2. device
Functions as displayed
Selectable options/Remarks
DEVICES line ## has ### devices
(c.2) select line (##−##)? ##
select device number
(###−###)? (555 = all) ###
− to select line and device number
line ## device ###: (zn. type ######)
1. name ###### 2. al.norm.######
>>>>>>>
3. alIncr.###### 4. drift ######
5. appl.w ###### 6. trouble ######
− to define the device type
− If during system startup function
2. autom. config.
is selected, then each device type is autom. recognized
and written into the data base
− enter ‘1. ok’ to open selection box
MT(DM)
manual call point
OP(DO)
wide spectrum smoke detector
DO1133
wide spectrum smoke detector (air sampling systems)
HI(DT)
heat detector
OH(DOT)
multi sensor smoke detector
DF1191
flame detector
DF1192
flame detector
EB
input module for signal contacts
ABI_in
input module for signal contact
1)
DC92coll
input module for conventional lines
CB320A
input module for SynoLINE 300
1) ABI... is a combined input-/output module with 2 independent channels (both must always be used)
1. name ###### 2. al.norm.######
>>>>>>>
− shows zone type (can only be changed on level ZONE)
− enter ‘2. ok’ to open selection box
DIRECT
LOCAL
3. alIncr.###### 4. drift ######
>>>>>>>
− to define the function of the danger signal on ‘increased sensitivity’
− enter ‘3. ok’ to open selection box
NONE
not used
DIRECT/ LOCAL
interpreted as Alarm 2 oder Alarm 1 depending on
zone type
INTEGR./
LOC.ITG
interpreted as Alarm 2 with verification
1)
INFO
interpreted as ‘warning’
1) only initiated if state ‘active’ has been reported during the last 10 polling cycles
Remark:
−
OP(DO)
and OH(DOT) initiate 2 danger signals:
− danger signal on ‘standard sensitivity’
− danger signal on ‘increased sensitivity’
3. alIncr.###### 4. drift ######
>>>>>>>
− to define the function of state DRIFT
− only available with device type OP(DO)and OH(DOT)
− enter ‘4. ok’ to open selection box
NONE
drift signal not processed
DRIFT
drift signal initiates state DRIFT
1), 2)
INFO
drift signal initiates state ‘warning’
1), 3)
1) only initiated if state DRIFT has been reported continously during the last 100 polling cycles
2) initiates STATUS message with buzzer (to be reset)
3) initiates STATUS message without buzzer (to be erased see page 64)
5. appl.w ###### 6. trouble ######
>>>>>>>
− to activate function ’application warning’
− only applies for OP(DO) and OH(DOT)
− enter ‘5. ok’ to open selection box
NONE
disabled
ACTIVE
status DRIFT 50x within 24h initiates message
’application warning’
5. appl.w ###### 6. trouble ######
>>>>>>>
− to define that ‘device fault’ initiates state ‘warning’ instead of state FAULT
− enter ‘6. ok’ to open selection box
FAULT
device fault initiates FAULT
INFO
device fault initiates ‘warning’