GST DC-9204E Quick Start Manual Download Page 1

 

30309265                                                                                                                                    Issue 1.04 

                                       

 

 

Features 

 

Alarm by pressing, reset by a special key. 

 

Plug-in structure. 

 

Standard: EN 54-11. 

Description 

DC-9204E  Innovation  Manual  Call  Point  (MCP)  is 

non-addressable.  It  alarms  by  the  output  current.  It 

can  be  simply  connected  to  compatible  conventional 

fire  alarm  system  from  various  manufacturers.  The 

MCP is suitable for public places. When there is a fire, 

pressing the frangible element on the MCP can send 

fire signal to fire alarm control panel.   

Connection and Cabling 

Terminals on the MCP base are shown as Fig. 1 (unit: 

mm).   

I+ I- O+ O-

 

Fig. 1 

I+, I-: Input signal, connecting with compatible control 

panel or the previous MCP. 
O+, O-: Output signal, connecting with the next MCP. 

Recommended Cabling 

0.5mm

2

 or above fire cable, subject to local codes

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 

 

 

 

 

 

 

 

 

Installation 

The  MCP  can  be  mounted  in  two  ways:  conduit 

embedded and surface mounting.   

Surface  Mounting:  First  install  the  back  box  into  the 

wall using 4 screws, and then install the base onto the 

back box. Connect cables to corresponding terminals 

as described above. Hook the juts of the MCP body to 

the base, and then press the part below the frangible 

element to combine them completely, as shown in Fig. 

2. 

Conduit  Embedded:  First  install  the  base  onto  the 

back  box, then  connect the  MCP  body  and the  base 

followed instructions above, as shown in Fig. 3. 

 

Back Box

Base

MCP Body

Lock Screw

Fig. 2 

 

 

DC-9204E   

Innovation Manual Call Point 

548g/07 

2831-CPR-F0129 

GST-0011-01 

 