background image

D900-08-00

1

I56-732-04

PS12/24ADA Series Strobes with

Mini-sounder for Fire Protective

Signaling Systems

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

NOTICE: 

This manual should be left with the owner/user

of this equipment.

General Description

The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the above appliances. It is recommended that
the installer be familiar with these requirements, with local
codes, and any special requirements of the local fire
authority having jurisdiction.
The Piezo electronic sounder and signaling strobe are
intended to be connected to the alarm indicating circuit of a
UL-listed fire alarm control panel. Both are compatible with
DC line supervision. The electronic sounder can be
connected to either 12 or 24 VDC panels. Models
PS2415ADA, PS2475ADA, PS24110ADA, and PS241575ADA
require 24 volt panels.  Models PS1215ADA and
PS121575ADA require 12 volt panels. Panels may have full-

Figure 1. Vertical and horizontal light distsribution:

LIGHT

–45˚

45˚

90˚

–90˚

                   Percent of
Degrees         Rating
   0              

100

5 - 25               90

30 - 45               75
  50                    55
  55                    45
  60                    40
  65                    35
  70                    35
  75                    30
  80                    30
  85                    25
  90                    25

Model

Supply

Voltage

Range

Operating Current from Regulated Supply

Operating Current from

Full-Wave Rectified Unfiltered Supply

Average

Operating

Current

Horn/

Strobe*

Peak

Current

(mA)

20/30V

Peak

Current

(mA)

10.5V/17V

Inrush

Current

(mA in

access of

Peak)

Average

Operating

Current

(mArms)

Horn/Strobe*

Peak Current

(mA)

20Vrms/

30Vrms

Peak Current

(mA)

10.5Vrms/

17Vrms

Inrush Current

(Amps in

excess

of Peak)

PS24110ADA
PS24110ADAW

20-30V

225

470/500

0

260

400/500

0.08

PS2475ADA
PS2475ADAW

20-30V

185

385/400

0

215

320/370

0.04

PS2415ADA
PS2415ADAW

20-30V

90

160/180

0

105

275/290

0.02

PS1215ADA
PS1215ADAW

12-17V

182

360/380

0

212

330/380

0.02

PS241575ADA
PS241575ADAW

20-30V

108

210/220

0

135

275/290

1

PS121575ADA
PS121575ADAW

12-17V

240

510/560

0

285

500/530

0.02

Average

Operating

Current

Strobe 

Only

210

170

75

170

93

225

Average

Operating

Current

(mArms)

Strobe Only

245

200

90

220

120

270

NOTE:

In-rush current du-
ration is less than
20 microseconds
(0.00002 seconds).

* Horn current is 12mA@12VDC, 15mA@24VDC

Table 1. PS12/24ADA Series Electrical Ratings

wave rectified, unfiltered power supplies. The strobes
produce  one flash per second (nominal) with continuous
nominal voltage applied.

The sounder/strobe strobe is rated for 0

°

 to 49

°

 C and is

NOT suitable for outdoor use.

The rated light output of the PS2415ADA, PS1215ADA,
PS241575ADA, and PS121575ADA is 15 cd  (See Figure 1).

The rated light output of the PS2475ADA is 75 cd  (See
Figure 1).

The rated light output of the PS24110ADA  is 110 cd (See
Figure 1).

NOTE:

The 15/75 cd strobe has been measured to be 75 cd
@ 0

°

 viewing angle.

firealarmresources.com