System Configuration
Operating Mode
[scconmen-300414-01.tif, 1, en_US]
Figure 3-18
Dialog for the SWT 3000 System Configuration
Table 3-30
Selection of the Operating Modes
Operating mode
Comment
Mode 1 (double system protection)
Possible with all variants
Mode 2 (single phase protection)
Possible with all variants
Mode 3 (switching functions)
Possible with all variants except VF1_CT and VF3_CT
Mode 3a (4 independent commands)
Only possible with the variants VF1_CT or VF3_CT
Mode 3b (2 plus 2)
Only possible with the variants VF1_CT or VF3_CT
Mode 4 (only one command active)
Possible with all variants
Mode 5A (3 independent commands)
Only possible with the variant VF1 M5A or VF3 M5A
Mode 5D
Only for digital transmission paths
Set the System mode as follows:
•
Select stand-alone for a stand-alone device.
•
Select integrated in PowerLink for a device integrated in PowerLink.
If the SWT 3000 device is not integrated in PowerLink, it is possible to configure the device as stand-alone.
On the other hand, if the device is inserted in PowerLink (iSWT), the system mode must be fixed as integrated
in PowerLink and allows no change.
The teleprotection signaling parameter is set as single purpose for stand-alone devices. The setting alternate
multi-purpose is also possible with a Siemens PLC system depending on the configuration and parameters of
the Siemens PLC system.
3.5.3
3.5.3.1
Installation and Commissioning
3.5 Device Configuration
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
125
C53000-G6040-C605-1, Edition 03.2020