[scconfom-111011-01.tif, 1, en_US]
Figure 3-42
Example of a System Configuration for a FOM Connection with 64 Kbps
All setting options for the interfaces are also shown in
. On the DLE module in each
case, the X.21 interface must be selected.
Refer also to
3.3.4.2 Jumper Settings for the Selection of Digital Line Interfaces LID-1
Settings for the Selection of Digital Line Interfaces LID-2
TPoP Configuration
Ethernet line interface is enabled in PowerSys of SWT 3000 > Configuration > System in
It supports 1+1 path protection with other analog or digital transmission path. The LED for unused LID-1 or
LID-2 is used for indication of Ethernet line connection status as described in
. The LED must be in
green color after the configuration is finished.
[ScEnTPoP-28032014-1, 1, --_--]
Figure 3-43
Ethernet Connection Selection
3.5.11
Installation and Commissioning
3.5 Device Configuration
150
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020