Figure 3-31
Example for Input Limitation Set to 50 ms
(1)
Input limitation 50 ms
Table 3-39
Setting Options for Input Command Extension to Minimum
Selection
Setting Options
Comment
Input command extension
min.
0 ms to 100 ms
In steps of 1 ms
0 = no extension
Default = 15 ms
If the commands at the binary input are shorter, they are extended to adjusted value. If they are longer, this
adjustment is irrelevant.
The following figure shows one command (red) at the binary input with a length of 10 ms. This command is
extended to 15 ms. The next command (blue) has a length of 30 ms. This command is not extended.
[dwinpext-130911-01.tif, 1, en_US]
Figure 3-32
Example for an Input Command Extension to Minimum 15 ms
(1)
Input Extension to minimum 15 ms