PU4 Test Command
The Dialog Commands
i
i
NOTE
The SWT 3000 > Commands dialog is only online available (when connected to SWT 3000).
In the PowerSys dialog SWT 3000 > Commands, it is possible to select lines, enable LID/FOM Loops, or to
enable the AMP measuring.
[sc_swt3000_commands, 1, --_--]
Figure 4-10
PowerSys Dialog SWT 3000 > Commands
The SWT 3000 > Commands dialog is divided into the following areas:
•
Line selection automatic (only if 2 transmission links are activated)
Automatic selection of the (primary) transmission line. If there is a fault, switchover to the alternative
(secondary) line.
•
Line selection primary (only if 2 transmission links are activated)
The SWT 3000 receiver is fixed to the primary transmission line. This setting causes the general alarm.
•
Line selection secondary (only if 2 transmission links are activated)
The SWT 3000 receiver is fixed to the secondary transmission line. If there is a line interrupt, switchover is
not possible. This setting causes the general alarm.
4.3
4.3.1
Diagnostics and Error Handling
4.3 PU4 Test Command
188
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020