Table 3-15
Assignment of Jumpers X43 to X58
Signal Input
250 V
110 V
48 V/60 V
24 V
BI1
X55 = inserted
X43 = open
X44 = open
X45 = open
X55 = open
X43 = inserted
X44 = open
X45 = open
X55 = open
X43 = open
X44 = inserted
X45 = open
X55 = open
X43 = open
X44 = open
X45 = inserted
BI2
X56 = inserted
X46 = open
X47 = open
X48 = open
X56 = open
X46 = inserted
X47 = open
X48 = open
X56 = open
X46 = open
X47 = inserted
X48 = open
X56 = open
X46 = open
X47 = open
X48 = inserted
BI3
X57 = inserted
X49 = open
X50 = open
X51 = open
X57 = open
X49 = inserted
X50 = open
X51 = open
X57 = open
X49 = open
X50 = inserted
X51 = open
X57 = open
X49 = open
X50 = open
X51 = inserted
BI4
X58 = inserted
X52 = open
X53 = open
X54 = open
X58 = open
X52 = inserted
X53 = open
X54 = open
X58 = open
X52 = open
X53 = inserted
X54 = open
X58 = open
X52 = open
X53 = open
X54 = inserted
[scifcjum-010813-01.tif, 1, en_US]
Figure 3-7
Position of jumpers X43 to X58
Test operation display
Test operation display
Operating LED
Operating LED
Installation and Commissioning
3.3 Jumper Settings for SWT 3000 Modules
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
111
C53000-G6040-C605-1, Edition 03.2020