Timer Settings for the Command Output
[sclimout-300414-01.tif, 1, en_US]
Figure 3-35
Setting Options for Limitation of the Output Command
Table 3-40
Setting Options for Limiting or Increasing the Output Time
Selection
Setting Options
Comment
Limitation of output
command
0 ms or 500 ms
0 = no limitation
The command in the following example is transmitted for 700 ms (Tx output). With the activated output limi-
tation, the command output is switched off after 500 ms.
[dwoutlim-150711-01.tif, 1, en_US]
Figure 3-36
Example of an Activated Output Command Limitation
(1)
Output limitation 500 ms
i
i
NOTE
Due to the limitation of 500 ms, an additional Rx-alarm occurs.
3.5.9.3
Installation and Commissioning
3.5 Device Configuration
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
143