[scpartab-140912-01.tif, 1, en_US]
Figure 6-16
snmpTargetParamsTable Settings
Table 6-8
snmpTargetParamsTable Settings
Field
Value
Target Paramter 1
snmpTargetParamsMPModel
SNMPv3(3)
snmpTargetParamsSecurityModel
USM(3)
snmpTargetParamsSecurityName
testuser
snmpTargetParamsSecurityLevel
authPriv(3)
snmpTargetParamsRowStatus
active(1)
Target Parameter 2
snmpTargetParamsMPModel
SNMPv2c(1)
snmpTargetParamsSecurityModel
SNMPv2c(2)
snmpTargetParamsSecurityName
public
snmpTargetParamsSecurityLevel
noAuthNoPriv(1)
snmpTargetParamsRowStatus
active(1)
•
3 - Create 2 new rows in table SNMP-TARGET-MIB::snmpTargetAddrTable
[scsnmpta-140912-01.tif, 1, en_US]
Figure 6-17
Create New Row in snmpTargetAddrTable
[scsnmpad-140912-01.tif, 1, en_US]
Figure 6-18
snmpTargetAddrTable List
Table 6-9
snmpTargetAddrTable Settings
Field
Value
Target Address 1
snmpTargetAddrName
addr1
snmpTargetAddrTDomain
snmpUDPDomain(.1.3.6.1.6.1.1)
snmpTargetAddrTAddress
192.168.20.10:162 (192.168.20.10:162)
SNMP and Remote Access
6.2 SNMP
288
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020