Display of the Entries in the Event Recorder
General Information
Protection commands and alarms of SWT 3000 are provided with time, date, and a registration number before
they are entered in the event memory.
The following events are entered:
•
Incoming protection commands from IFC-D/P
•
Outgoing protection commands to the IFC-D/P
•
Detected alarms
•
Program restart
•
Changing date and/or time
•
Changing the configuration
Up to 8000 non volatile event entries with a time resolution of 1 ms are possible. The service PC reads out the
entries. The readout is also possible from the remote station with remote monitoring. If there is an overflow,
the oldest entry in the event memory is overwritten.
The event recorder can only be read when the PowerSys program is connected to the device (PowerLink with
integrated SWT 3000 or stand-alone SWT 3000). The submenu Event recorder is available in SWT 3000 >
Information.
[sceventr-091111-01.tif, 1, en_US]
Figure 4-11
SWT 3000 > Information > Event Recorder
(1)
Selection of number of events
(2)
Selection of type of events
The number and type of events is selectable as shown in the preceding figure. You cannot clear the event
recorder.