![Siemens SIWAREX WP251 Manual Download Page 137](http://html.mh-extra.com/html/siemens/siwarex-wp251/siwarex-wp251_manual_374538137.webp)
Scale parameters and functions
8.27 DR 30 Process state
SIWAREX WP251
Manual, 12/2015, A5E37203357A
137
Variable
Note
Type
Length
(bytes)
RW De-
fault
Min. Max.
Modbus
regis-
ters
Error Clock
Set when buffering of the
time has failed. Is cleared
after the time is set.
B16_5
0
r
0
-
-
3005
Trace active
Set when trace is running
B16_6
0
r
0
-
-
3005
Cmd error at digital
input
Set when error occurs re-
sulting from command at
digital input
B16_7
1
r
0
-
-
3005
Calibration curve not Points of the calibration
curve are not plausible or
are incomplete
B16_8
0
r
0
-
-
3005
Service mode
Service mode is activated
B16_9
0
r
0
-
-
3005
Simulation mode
Simulation mode is activat-
ed
B16_10
0
r
0
-
-
3005
Write protection
Write protection is active
(jumper set)
B16_11
0
r
0
-
-
3005
Analog output error
Analog output error
B16_12
0
r
0
-
-
3005
Stand-alone opera-
tion
Set when stand-alone oper-
ation is selected at DIP
switch
B16_13
0
r
0
-
-
3005
Start up
Startup has taken place or
factory settings have been
loaded (is deleted again
after 5 seconds)
B16_14
0
r
0
-
-
3005
Error
Error is present (operating
error)
B16_15
1
r
0
-
-
3005
AWI
Status
Weighing step 0
Dosing is in step 0
B16_0
0
r
0
-
-
3006
Weighing step 1
Dosing is in step 1
B16_1
0
r
0
-
-
3006
Weighing step 2
Dosing is in step 2
B16_2
0
r
0
-
-
3006
Weighing step 3
Dosing is in step 3
B16_3
0
r
0
-
-
3006
Weighing step 4
Dosing is in step 4
B16_4
0
r
0
-
-
3006
Weighing step 5
Dosing is in step 5
B16_5
0
r
0
-
-
3006
Weighing step 6
Dosing is in step 6
B16_6
0
r
0
-
-
3006
Weighing step 7
Dosing is in step 7
B16_7
1
r
0
-
-
3006
Post dosing active
Automatic post-dosing is
active
B16_8
0
r
0
-
-
3006
Coarse signal
Coarse signal is active
B16_9
0
r
0
-
-
3006
Fine signal
Fine signal is active
B16_10
0
r
0
-
-
3006
Reserve
Reserve
B16_11
0
r
0
-
-
3006
Emptying signal
Emptying signal is active
B16_12
0
r
0
-
-
3006
Weighing cycle
stopped
Dosing has been stopped
B16_13
0
r
0
-
-
3006
Check stop active
Dosing in check stop
B16_14
0
r
0
-
-
3006
Check stop follows
Check stop command is-
sued, check stop will occur
at next check stop point
B16_15
1
r
0
-
-
3006