6
OPERATION
88
SITRANS FX330
www.siemens.com/flow
05/2016 - A5E36751269-AA
F
Configuration
Inconsistent NVRAM
Inconsistent data in the
parameter memory
Perform a hard reset. If the
message recurs, contact the
manufacturer.
Error Starting SIL Mode
Error in starting SIL mode
Perform the SIL starting
process as described in the
safety manual. If the
message recurs, contact the
manufacturer.
CO Float Error
Error in processing of the
measuring value due to
inconsistent set of
parameter.
Load the factory settings
and perform a hard reset. If
the message recurs, contact
the manufacturer.
NVRAMs Mismatch
Incompatible serial
numbers of display and
electronic module
Use displays and electronic
modules, which belong
together. Contact the
manufacturer, if necessary.
Conv. NVRAM Layout Error
Incompatible data in
parameter memory
Perform a hard reset. If the
message recurs, contact the
manufacturer.
Disp. NVRAM Layout Error
Incompatible data after
firmware update
Perform a hard reset. If the
message recurs, contact the
manufacturer.
C
Sensor
Sensor FW Update
A firmware update of the
sensor module has been
started.
Wait for firmware update to
finish.
C
Electronics
Converter FW Update
A firmware update of the
converter module has been
started.
Wait for firmware update to
finish.
C
Configuration
Sensor Sim. Active
A simulation of the sensor is
active
Stop the simulation of the
sensor variables
Current Out. Sim. Active
A simulation of the current
output is active
Stop the simulation of the
current output variables
Current In. Sim. Active
A simulation of the current
input is active
Stop the simulation of the
current input variables
HART Sim. Active
Simulation of a measuring
value via HART
®
interface
Stop the simulation via the
HART
®
interface.
Flow Comp. Sim. Active
A simulation of
measurement value
processing is active.
Stop the simulation of the
measurement value
processing.
Binary Output Sim. Active
A simulation of the binary
output is active
Stop the simulation of the
binary output variables
Totalizer Sim. Active
A simulation of the totalizer
is active
Stop the simulation of the
totalizer variables
SIL Prooftest
Device is in maintenance
mode 3 (proof test for SIL)
Perform the test according
to the instruction in the
safety manual.
Parameterization Test
Device is in maintenance
mode 3 (parameterization
test)
Status
type
Event group
Single event
Description
Actions to eliminate the
event