05/2016 - A5E36751269-AA
6.7.4 Menu description "A Quick Setup"
Function
Setting / Description
A1 Language
Available display languages: German, English and French
22 more languages in preparation (for details refer to
Menu languages
on page 55)
A2 Contrast
Adjust contrast of local display (-10...+10; Standard = 0)
A3 Login
Enter password: 0000 (to change password refer to menu C6.2.2)
A4 Tag
Entry and display of measuring point identifier (8 digits).
A5 Long Tag
Entry and display of long measuring point identifier (1...32 digits).
Entry will be displayed in the header bar on the LC display (depending on letter size,
min. 11 digits can be displayed).
A6 Message View
NAMUR messages (F, S, M, C, I)
For further information refer to
Status messages and diagnostic information
on page
86.
A7 Fluid
Select: Liquid / Steam / Gas / Wet Gas / Gas Mixture
Depending on selected fluid, appropriate medium can be selected in A8
A8 Medium
If fluid is "Gas" or "Wet Gas" (for details refer to
Gas options for gas measurement
on
page 56)
The following selection is available for fluid = "Steam":
Saturated Steam / Superheated Steam / Custom
The following selection is available for fluid = "Liquid":
Water / Custom
The following selection is available for fluid = "Wet Gas":
Here, a gas can be selected as a wet gas from all of the above mentioned gases.
A9 Units
For further information refer to menu C6.5.
A10 Meter Type
Standard:
For liquids, gases and steam; integrated temperature compensation for saturated
steam.
Heat:
For liquids, gases and steam; integrated temperature compensation for saturated
steam, gross/net heat measurement for saturated steam and water.
Heat & Dens. by Pres.:
Integrated density compensation for saturated steam, superheated steam and gas,
gross/net heat measurement for saturated steam, superheated steam and water.
Heat & Dens. & FAD:
Integrated density compensation for saturated steam, superheated steam and gas,
gross/net heat measurement for saturated steam, superheated steam and water, FAD
functionality.
A11 Application Assistant
For details refer to next tables.
A12 Cluster Checks
For further information refer to
A12 plausibility checks
on page 91.