6
OPERATION
74
SITRANS FX330
www.siemens.com/flow
05/2016 - A5E36751269-AA
6.7.5 Menu description "B Test"
For simulation and actual values refer to
Menu overview "B Test" on page 61.
6.7.6 Menu description "C Setup"
For further information refer to
Menu overview "C Setup" on page 62.
There are four different meter types (software versions) available for the signal converter:
Depending on the ordered meter type those options may have been ordered and are already
activated or can be activated in menu "C6.3 Extras". For this purpose an activation password is
necessary. Please contact the manufacturer.
When using the standard device all menu entries concerning heat measurement, density
calculation and FAD are hidden.
Meter type
Description
Standard
Uncompensated measurement for liquids, gases and steam; integrated temperature
compensation included for saturated steam
Heat
Same as "Standard", plus gross/net heat measurement for saturated steam and hot
water
Heat & Dens. by Pres.
Same as "Heat", plus gross/net heat measurement for superheated steam; density
compensation for the measurement of gas
Heat & Dens. & FAD
Same as "Heat & Dens. by Pres.", plus FAD (Free Air Delivery) measurement
Function
Setting / Description
C1 Process
C1.1 Fluid
Select: Liquid / Steam / Gas / Wet Gas / Gas Mixture
Appropriate media can be selected in menu C1.2 dependent on selected fluid type.
C1.2 Medium
If fluid = "Liquid":
Water / Custom
If fluid = "Steam":
Saturated Steam / Superheated Steam / Custom
If fluid is "Gas" or "Wet Gas" (for details refer to
Gas options for gas measurement
on
page 56)
C1.3 Gas
This menu is available if fluid = "Wet Gas" or "Gas Mixture", or if medium = "Air".
Here the gas composition or gas properties can be defined.
C1.3.1 Gas Mixture
This menu is available for fluid = "Gas Mixture".
Enter gas mixture as percentage share of gas options (for details refer to
Gas options
for gas measurement
on page 56)
C1.3.2 Relative Humidity
This menu is available if fluid = "Wet Gas". Enter: 0
…
100%
C1.3.3 Inlet Temperature
The menus C1.3.3 to C1.3.9 are part of the FAD functionalities. They are available, if
fluid = "Gas", medium = "Air" and FAD functionality is included in the meter type option.
Enter ambient temperature of the compressor inlet side in selected temperature unit
(C6.5.19).
C1.3.4 Atm. Pressure
Enter ambient pressure of the compressor inlet side as value in selected pressure unit
(C6.5.17).
C1.3.5 Filter Pressure Drop
Enter pressure drop of compressor filter in selected pressure unit (C6.5.17).
C1.3.6 Inlet Rel. Humidity
Enter relative air humidity of the compressor inlet side as 0
…
100%.
C1.3.7 Outlet Rel. Humidity
Enter relative air humidity of the compressor outlet side as 0
…
100%.