Maintenance and Troubleshooting
8-4
7SS60 Manual
E50417-G1176-C132-A2
8.3
Troubleshooting
8.3.1
7SS601 measuring system
If the device indicates a defect, the following procedure is recommended:
If none of the LEDs on the front panel of the device is on, then check:
q
Has the module been properly pushed in and locked?
q
Is the auxiliary voltage available with the correct polarity and of adequate magni-
tude, connected to the correct terminals (block circuit diagrams are given in Appen-
dix A.2 and A.3)?
q
Has the mini-fuse in the power supply section blown? If required, replace the mini-
fuse according to the section “Replacing the mini-fuse” below.
If the red fault indicator LED is on and the green ready LED remains dark, re-initializa-
tion could be tried by switching the auxiliary voltage off and on again.
This, however, results in loss of parameter settings in a parameterizing process has
not yet been completed. Additionally, date and time must be set again (refer to chapter
4.2.5).
Replacing the mini-
fuse
q
Select a replacement fuse 5 x 20 mm (refer to Section A.4). Ensure that the rated
value, time lag (slow) and code letters are correct.
q
Prepare the area of work: provide a conductive surface for the module.
q
Slip away the covering caps at the top and bottom of the housing, making accessi-
ble one screw each in the top and bottom center. Unscrew these two screws.
q
Pull out the module by taking it at the front panel and place it on the conductive sur-
face.
..
q
Remove the blown fuse from the holder.
q
Fit the new fuse into the holder.
q
Insert the module in the housing.
q
Fix the module in the housing by tightening the two fixing screws.
Switch the device on again. If a power supply failure is still signalled, a fault or short-
circuit is present in the internal power supply. The device should be returned to the
factory (refer to chapter 8.4).
Warning!
Hazardous voltages can be present in the device even after disconnection of the sup-
ply voltage (storage capacitors!).
Warning!
Electrostatic discharges via the component connections, the p.c.b. tracks or the con-
necting pin must be avoided under all circumstances by previously touching an
earthed metal surface.
Summary of Contents for SIPROTEC 7SS60
Page 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Page 2: ......
Page 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Page 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Page 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Page 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Page 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...