Technical Data
9-7
7SS60 Manual
E50417–G1176–C132–A2
9.1.2.3
7TS720 command output module
Auxiliary voltage
Rated auxiliary voltageU
H
48/60 Vdc
(38 to 72 Vdc)
(permissible voltage range)
110/125 Vdc
(88 to 150 Vdc)
220/250 Vdc
(176 to 300 Vdc)
settable, see Figure A-8
as delivered: 220/250 Vdc
Power
consumption
Rated auxiliary voltage
max. power consumption, continuous
48 V
0.7 W
60 V
1.0 W
110 V
1.9 W
125 V
2.4 W
220 V
3.1 W
250 V
3.9 W
Command contacts
Number of relays
8
Contacts per relay
2 NO contacts
for short-term operation < 10 s
1)
Pickup time
approx. 7 ms
Switching capacity
MAKE
1000 W/VA
BREAK
30 W/VA
Switching voltage
250 V ac/dc
permissible current
continuous
5 A
0.5 s
30 A
Weight
approx. 0.5 kg
1)
limited by the continuous power dissipation of the device
9.1.3
Peripheral module housing
Design
Housing
7XP204
1
/
2
19"
Dimensions
see Figure 9-2
Weight
approx. 3.5 kg
Degree of protection according
to IEC 60529-1
for the device
IP 51 (front)
IP 20 (rear)
for operator protection
IP 2X (if all connectors and blanking plates
are fitted)
Summary of Contents for SIPROTEC 7SS60
Page 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Page 2: ......
Page 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Page 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Page 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Page 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Page 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...