Appendix
A-19
7SS60 Manual
E50417-G1176-C132-A2
A.7
Overview of parameters
DIGSI
addr.
Parameter
Possible settings
Default setting
Explanation
1101
01 FREQ
50 Hz
60 Hz
50 Hz
Rated frequency of power system
1134
01 T-TRP
0.01s to 32.00 s
0.15 s
Minimum duration of TRIP command
1135
01 L.Out
OFF
ON
ON/butt.
OFF
Lockout function
1501
10BUSBAR
PROTECT.
ON
OFF
BLO.TRP
ON
Busbar protection function
1505
10Id>
0.20 Ino
1
to 2.50 Ino
1
1 I
no
: normalized rated current; I
no
= 100 mA with a symmetrical rated current flowing at the primary side
1.00 Ino
1
Minimum threshold for differential current
1506
10K fac
0.25 to 0.80
0.60
Sensitivity to internal faults
1511
10 TrpDly
0.00 to 10.00 s
0.00 s
Time delay of trip
1801
13Id Sup
bl/relBP
bl/ackBP
ALRMonly
OFF
bl/relBP
State of supervision of the differential
current function
1802
13Id thr
0.10 Ino
1
to 1.00 Ino
1
0.15 Ino
1
Threshold of differential current supervision
7101
71LANGUA
ENGLISH
DEUTSCH
ENGLISH
Selection of the operating language
7201
72DEVICE
minimum setting:..... .....1
maximum setting:.....254
1
ID number of the device within the
substation
7202
72FEEDER
minimum setting:..... .....1
maximum setting:.....254
1
Number of feeder within the substation
(feeder address)
7203
72SUBSTA
minimum setting:..... .....1
maximum setting:.....254
1
ID number of substation, if more than one
substation can be addressed
7211
72 PC-INT
DIGSI V3
ASCII
DIGSI V3
Data format for the interface
7214
72 GAPS
minimum setting: .....0.0 s
maximum setting: ....5.0 s
1.0 s
Maximum permissible transmission gap
between telegrams for modem transmission
7215
72PCBAUD
1200 Baud
2400 Baud
4800 Baud
9600 Baud
19200 Baud
9600 Baud
Transmission baud rate for serial
PC- interface
7216
72 PARITY
DIGSI V3
8O1
8N2
8N1
DIGSI V3
Parity of transmission telegrams
7410
74-T MAX
0.20 s to 5.00 s
1.50 s
Maximum time period of a fault recording
7411
74 T-PRE
0.05 s to 1.50 s
0.30 s
Pre-trigger time for fault recording
7412
74 T-POS
0.05 s to 1.50 s
0.20 s
Post-fault time for fault recording
Summary of Contents for SIPROTEC 7SS60
Page 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Page 2: ......
Page 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Page 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Page 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Page 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Page 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...