Control in Operation
6-4
7SS60 Manual
E50417-G1176-C132-A2
Faults in the primary switchgear are indicated only with “Fault” and a consecutive fault
number. Detailed information on the sequence of events during a fault is contained in
the block “Fault annunciations”.
Fault
annunciations
Block 82
Here the annunciations of the last eight faults can be read out. These are sorted from
the newest to the oldest in a subordinate level of block 82. When a ninth fault arrives,
the system deletes the data of the oldest one. Each of the eight fault buffer can store
up to 30 annunciations. If more events are issued, the oldest are overwritten.
As long as the date and time of the device have not been set, the date and time dis-
played are the relative date and time since the last startup of the processor system.
Next, the fault events are displayed in the chronological order of their detection, with
a relative time referred to the moment at which the fault started.
Pressing the
key brings you from block
)$8/7$1181&
(
) to the fault
annunciations, where you can call up successively all fault annunciations using the
and
keys.
To move from the selected fault annunciation to the fault annunciation buffer, press
the
key.
Just like the operational annunciations, the fault annunciations are stored in lists. Use
the
and
keys to scroll though the lists.
Measured values
Block 84
Measured values for the differential and restraint current can be displayed in block 84.
Values are shown in percent of the nominal values. A prerequisite for correct display
is that the nominal data have been correctly set in block 00.
Pressing the
key brings you from block
0($69$/8(6
(
) to the mea-
sured values, which can now be called up successively using the
and
keys.
The values are updated during the read-out. When scrolling within the block with the
or
key, the updated values are displayed.
Annunciation
buffer
PV
Display
)$8/7
PV
)7GHW
PV
',)7US
Summary of Contents for SIPROTEC 7SS60
Page 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Page 2: ......
Page 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Page 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Page 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Page 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Page 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...