Technical Data
9-5
7SS60 Manual
E50417–G1176–C132–A2
9.1.2
Peripheral modules
9.1.2.1
7TM700 restraint/command output module
Measuring input I
s
Number of restraint units
5
Rated current
100 mA
Rated frequency
16.7Hz, 50 Hz, 60 Hz
Dynamic overload capability
250 x I
N
one half cycle
(pulse current)
Thermal overload capability (rms)
100 x I
N
for
≤
1 s
(where external summation or matching 30 x I
N
for
≤
10 s
current transformers are used,
4 x I
N
continuous
their limit data must be observed)
Auxiliary voltage
Rated auxiliary voltage U
H
48/60 Vdc
(38 to 72 Vdc)
(permitted voltage range)
110/125 Vdc
(88 to 150 Vdc)
220/250 Vdc
(176 to 300 Vdc)
settable, see Figure A-5
As delivered: 220/250 Vdc
Power
consumption
Rated auxiliary voltage
max. power consumption, continuous
48 V
0.7 W
60 V
1.0 W
110 V
1.9 W
125 V
2.4 W
220 V
3.1 W
250 V
3.9 W
Command contacts
Number of relays
5
Contacts per relay
2 NO contacts
for short-term operation < 10 s
1)
Pickup time
approx. 7 ms
Switching capacity
MAKE
1000 W/VA
BREAK
30 W/VA
Switching voltage
250 V ac/dc
Permissible currents
continuous
5 A
0.5 s
30 A
Weight
approx. 2.0 kg
1)
limited by the continuous power dissipation of the device
Summary of Contents for SIPROTEC 7SS60
Page 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Page 2: ......
Page 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Page 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Page 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Page 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Page 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...