Configuration
4-10
7SS60 Manual
E50417-G1176-C132-A2
If a selection place is to be assigned to physical unit, selection is made with the func-
tion
QRWDOO
(not allocated).
Leave the selection level for signal relay 1 with key
. You can then go to the next
signal relay with the arrow key
.
Note on Table 4-4:
Annunciations which are indicated by a leading “
!µ
sign represent the direct confirma-
tion of the binary inputs and are identical with them. They are available as long as the
corresponding binary input is energized.
Table 4-4
Marshallable output functions
FNo.
Text on the LC display
Logical functions
1
5
7701
7721
7900
7901
7910
7911
7914
7920
7921
not all.
>LED r.
>LO Res
Lockout
>BP blo
>BP bPu
BP blk.
BP act.
BP Trip
IdS act
IdS flt
Not allocated
>Reset LED indicators
>Lock Out reset
Lock Out state
>Block busbar protection
>Busbar protection blocking pulse
Busbar protection blocked
Busbar protection active
Busbar protection: Trip
IDIFF supervision active
IDIFF supervision: fault detected
Table 4-5
Presettings of signal relays
4th level
5th level
FNo.
Remark
MARSHALLING
Signal relays
Block heading
62 MARSH SIG.RE 2
6 2 S I G 2 1
B P T r i p
7914
Busbar protection: Trip
62 MARSH SIG.RE 3
6 2 S I G 3 1
BP blk.
7910
Busbar protection blocked
Summary of Contents for SIPROTEC 7SS60
Page 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Page 2: ......
Page 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Page 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Page 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Page 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Page 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...