Technical Data
9-2
7SS60 Manual
E50417–G1176–C132–A2
9.1
General data
9.1.1
7SS601 measuring system
Measuring input I
d
Rated current
100 mA
Rated frequency
50/60 Hz can be set, 16.7 Hz
Dynamic overload capability
250 x I
N
one half cycle
(pulse current)
Thermal overload capability (rms)
100 x I
N
for
≤
1 s
(where external summation or matching 30 x I
N
for
≤
10 s
current transformers are used, their limit 4 x I
N
continuous
data must be observed)
Isolating voltage
2.5 kV (rms)
Measuring range for operational
0 to 240 %
measured values
Measuring dynamics
100 x I
N
without offset
50 x I
N
with full offset
Measuring input I
R
Rated current
1.9 mA
Dynamic overload capability
250 x I
N
for 10 ms
(pulse current)
Thermal overload capability (rms)
100 x I
N
for
≤
1 s
(where external summation or matching 30 x I
N
for
≤
10 s
current transformers are used, their limit 4 x I
N
continuous
data must be observed)
Isolating voltage
2.5 kV (rms)
Measuring dynamics
0 to 200 x I
N
Auxiliary voltage
via integrated dc/dc converter
24/48 Vdc
(19 to 58 Vdc)
Rated auxiliary voltage U
H
60/110/125 Vdc
(48 to 150 Vdc)
(permissible variations)
220/250 Vdc
(176 to 300 Vdc)
115 Vdc
(92 to 133 Vac)
Superimposed ac voltage
≤
15 % of rated voltage
peak to peak
Power consumption
quiescent
approx. 3 W
energized
approx. 5 W
Bridging time during failure/short-circuit
≥
50 ms at U
H
≥
100 Vdc
of auxiliary voltage
≥
20 ms at U
H
≥
48 Vdc
Summary of Contents for SIPROTEC 7SS60
Page 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Page 2: ......
Page 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Page 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Page 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Page 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Page 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...