Functions
5-15
7SS60 Manual
E50417-G1176-C132-A2
5.3.2
Hints on setting
Rated system
frequency
The default setting is
+]
; it needs to be changed only for a system frequency of
+]
.
16.7 Hz are available in a version with separate order no.
Lockout function
If the Lockout function is set to
21
, the lockout state can only be reset via a binary
input. If
21EXWW
is set, the lockout can be reset with the N key or with a binary input.
5.3.3
Overview of parameters
5.3.4
Annunciations
Note:
The parameter
)5(4
(
) can only be called up in versions for 50 Hz or 60 Hz.
In systems with a rated frequency of 16.7 Hz, the parameter
)5(4
(
) is not
displayed at all.
DIGSI
addr.
Parameter
Possible settings
Default setting
Explanation
1101
01 FREQ
50 Hz
60 Hz
50 Hz
Rated frequency of power system
1134
01 T-TRP
0.01 s to 32.00 s
0.15 s
Minimum duration of TRIP command
1135
01 L.Out
OFF
ON
ON/key
OFF
Lockout function
FNo.
Text on LC display
Logical functions
7721
LockOut
Lockout state
Summary of Contents for SIPROTEC 7SS60