Functions
5-19
7SS60 Manual
E50417-G1176-C132-A2
5.4.3
Overview of parameters
5.4.4
Annunciations
Check zone protection
Condition
Setting of
10 K fac (1506)
none
0.3
DIGSI
addr.
Parameter
Possible settings
Default setting
Explanation
1501
10BUSBAR
PROTECT.
ON
OFF
BLO.TRP
ON
Busbar protection function
1505
10Id>
0.2 I
no
1
to 2.50 I
no
1
1 I
no
: normalized rated current; I
no
=100mA with a symmetrical rated current flowing on the primary side
1.00 I
no
1
Threshold for differential current
1506
10K fac
0.25 to 0.80
0.60
Sensitivity to internal faults
1511
10 TrpDly
0.00 to 10.00
0.00
Time delay of trip
FNo.
Text on LC display
Logical functions
7721
LockOut
Lock Out state
7911
BP act.
Busbar protection active
7914
BP Trip
Busbar protection: Trip
7915
BP Tdel
Busbar protection: Delay time started
7922
BIPulS.
Supervision of blocking pulse