Getting Started
3-4
7SS60 Manual
E50417-G1176-C132-A2
7SS601
measuring system
q
Connect the earth of the device to the protective earth of the location. Units for cu-
bicle or panel flush mounting have the earthing screws on their back.
q
The green Service/Betrieb LED on the front plate must light after at most 0.5 s, and
the red Blocked/Störung LED must go off after at most 10 s.
q
After at most 15 s the start-up messages indicating the ordering code and the firm-
ware version must disappear from the display. Instead, the measured values of the
differential current I
d
and the restraint current I
R
should appear. Depending on the
preset marshalling, some of the LEDs may light already.