INSTALLATION   

 

 

 

  

INSTRUCTIONS

   

 

 

 

 

 

 

 

Submersible Pump Protector 
MODEL SPP-235P 

 
 
 

 

II_S

PP-235

P_A1

  

293 Wright Street, Delavan, WI  53115 

 (866) 9-PENTEK

 

 

Содержание Pentek SPP-235P

Страница 1: ...INSTALLATION INSTRUCTIONS Submersible Pump Protector MODEL SPP 235P II_SPP 235P_A1 293 Wright Street Delavan WI 53115 866 9 PENTEK...

Страница 2: ...ontrol box If the location is wet or dusty a NEMA 3R 4 or 12 enclosure should be used The Submersible Pump Protector must be protected by a fuse or circuit breaker 2 Connect a current transformer CT t...

Страница 3: ...Size Current CT 5 7 HP 27 5 42 1 50 5 10 HP 51 75 5 15 HP 75 100 5 TABLE 1 Current Transformer Selection FIGURE NO 1 Typical Wiring Diagram 3...

Страница 4: ...4...

Страница 5: ...he RESTART DELAY CALIBRATION knob to CAL while pumping Wait for the pump to turn off approximately 10 seconds then adjust the RESTART DELAY CALIBRATION knob to the desired setting SENSITIVITY The Subm...

Страница 6: ...60 second period The Submersible Pump Protector is capable of detecting a rapid cycle condition whether a control device such as a pressure switch is installed before or after it Upon detecting eithe...

Страница 7: ...Submersible Pump Protector remove and re apply power Note Protection against rapid cycling of a control device installed after the Submersible Pump Protector is always enabled Disabling line side det...

Страница 8: ...e to a dry run or dead head condition The unit is timing through the restart delay and will try to restart Check for restricted flow or inadequate supply of liquid Off Blinking OVERCURRENT The Submers...

Страница 9: ...PHYSICAL DIMENSIONS 4 05 102 87 5 26 133 60 4 50 114 30 375 9 53 2 93 74 42 FRONT VIEW 2 17 55 12 2 90 73 66 BOTTOM VIEW 9...

Страница 10: ...age 230VAC Load Range 5 to 15hp external current transformer required Frequency 50 60 Hz note 50Hz will increase all delay timers by 20 Output Characteristics Output Contact Rating SPST 720VA 240VAC G...

Страница 11: ...11 NOTES...

Страница 12: ...ure provided such goods have not been subjected to misapplication misuse negligence or repairs by unauthorized persons This Warranty does not apply to any faulty performance caused by improper voltage...