Functions
5-11
7SS60 Manual
E50417-G1176-C132-A2
Normal earth
current sensitivity
In a connection circuit as shown in Figure 5-10, the sensitivity to the earth current is
less pronounced than in the circuit shown in Figure 5-6. It should be considered for
power systems with low-resistant or solid earthing of the starpoints where due to the
transformer design sufficiently high short-circuit currents can be expected in case of
1-phase earth faults.
Figure 5-10 Connection circuit of the summation current transformer for normal earth
short-circuit sensitivity
The effective number of turns in the winding and fault detection ranges are listed in the
following table.
Figure 5-11 Summation transformer currents in a 1-pole earth fault in a power system with earthing only on the consumer
side; connection as per 5-10
Short-circuit
Affected phases
Effective number
of turns
Fault detection
range
Multiple of I
N
3-phase
L1–L2–L3
√
3
0.20 to 2.50
2-phase
L1–L2
L2–L3
L3–L1
1
2
1
0.35 to 4.33
0.18 to 2.17
0.35 to 4.33
1-phase
L1–E
L2–E
L3–E
2
1
3
0.18 to 2.17
0.35 to 4.33
0.12 to 0.72
more
devices
Summary of Contents for SIPROTEC 7SS60
Page 1: ...E50417 G1176 C132 A2 SIEMENS SIPROTEC 7SS60 V3 1 Centralized Numerical Busbar Protection ...
Page 2: ......
Page 4: ...Siemens Aktiengesellschaft Document No E50417 G1176 C132 A2 ...
Page 8: ...Preface iv 7SS60 Manual E50417 G1176 C132 A2 ...
Page 50: ...Configuration 4 16 7SS60 Manual E50417 G1176 C132 A2 ...
Page 80: ...Control in Operation 6 8 7SS60 Manual E50417 G1176 C132 A2 ...
Page 112: ...Technical Data 9 18 7SS60 Manual E50417 G1176 C132 A2 ...