Appendix
A-13
7SS60 Manual
E50417-G1176-C132-A2
Command output
module 7TS720
Figure A-8
Location of the jumpers on the 7TS720 command output module (delivery status)
220/250V
110/125V
48/60V
X21
4
3
2
1
220/250V
110/125V
48/60V
X22
4
3
2
1
220/250V
110/125V
48/60V
X23
4
3
2
1
220/250V
110/125V
48/60V
X24
4
3
2
1
220/250V
110/125V
48/60V
X25
4
3
2
1
220/250V
110/125V
48/60V
X26
4
3
2
1
220/250V
110/125V
48/60V
X27
4
3
2
1
220/250V
110/125V
48/60V
X28
4
3
2
1
X1
X2
Jumper
Rated auxiliary voltage
48 / 60 Vdc
110 / 125 Vdc
220 / 250 Vdc
X21
1–2
2–3
3–4
X22
1–2
2–3
3–4
X23
1–2
2–3
3–4
X24
1–2
2–3
3–4
X25
1–2
2–3
3–4
X26
1–2
2–3
3–4
X27
1–2
2–3
3–4
X28
1–2
2–3
3–4